dcmim2ConfigSysLowTempReset
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.9.3.1.4
Object
scalar
mandatory
r/w
Integer32
Level at which System Low Temp alarm condition is reset (cleared). Range (lower temp + 3) to 13 (degC). Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius or Fahrenheit).
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.9.3.1.4- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- dcmim2ConfigSystem
- Siblings
- 3
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| dcmim2ConfigSysHighTempTrip mandatory Trip level (threshold) at which System High Temp alarm condition is created.
Range 28 to 100 (degC).
Values are represented in thousandths of a degree.
Units are displa… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.9.3.1.1 |
| dcmim2ConfigSysHighTempReset mandatory Level at which System High Temp alarm condition is reset (cleared).
Range 25 to (upper temp - 3) (degC).
Values are represented in thousandths of a degree.
Units are di… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.9.3.1.2 |
| dcmim2ConfigSysLowTempTrip mandatory Trip level (threshold) at which System Low Temp alarm condition is created.
Range -100 to 10 (degC).
Values are represented in thousandths of a degree.
Units are displayed in the … | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.9.3.1.3 |