battManSystemConfigurationInvalid
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.16.8.10
Object
scalar
mandatory
Enumeration
When set to alarm(2), indicates that the system is not configured correctly.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.16.8.10- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- battManSystemStatus
- Siblings
- 10
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | normal |
2 | alarm |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| battManSystemAmbientTempC mandatory The system ambient temperature in tenths of degrees Celsius. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.16.8.1 |
| battManSystemSuspendVoltage mandatory When set to alarm(2), indicates that the system has suspended voltage scans. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.16.8.11 |
| battManSystemAmbientTempF mandatory The system ambient temperature in tenths of degrees Fahrenheit. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.16.8.2 |
| battManSystemPilotTempC mandatory The system pilot temperature in tenths of degrees Celsius. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.16.8.3 |
| battManSystemPilotTempF mandatory The system pilot temperature in tenths of degrees Fahrenheit. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.16.8.4 |
| battManSystemAmbientHighTempAlarm mandatory When set to alarm(2), indicates that the system has a high temperature alarm. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.16.8.5 |
| battManSystemAmbientLowTempAlarm mandatory When set to alarm(2), indicates that the system has a low temperature alarm. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.16.8.6 |
| battManSystemPilotBatteryHighTempAlarm mandatory When set to alarm(2), indicates that the system has a pilot battery high temperature alarm. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.16.8.7 |
| battManSystemPilotProbeDisconnected mandatory When set to alarm(2), indicates that the system pilot probe is disconnected. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.16.8.8 |
| battManSystemAmbientProbeDisconnected mandatory When set to alarm(2), indicates that the system ambient probe is disconnected. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.16.8.9 |