atsStatusPhaseSyncStatus
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.8.5.1.14
Object
scalar
mandatory
Enumeration
This variable returns the status of the phase synch.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.8.5.1.14- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- atsStatusDeviceStatus
- Siblings
- 21
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | inSync |
2 | outOfSync |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| atsStatusCommStatus mandatory This variable returns the current communication status
of the Automatic Transfer Switch. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.1 |
| atsStatusSwitchStatus mandatory This variable returns the status of the ATS. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.10 |
| atsStatusFrontPanel mandatory This variable returns the present state of the ATS front panel.
locked(1): Front panel button cannot be used to change the sources.
unlocked(2): Front panel button can be used to … | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.11 |
| atsStatusSourceAStatus mandatory This variable returns the status of the Source A. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.12 |
| atsStatusSourceBStatus mandatory This variable returns the status of the Source B. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.13 |
| atsStatusVoltageOutStatus mandatory This variable returns the output voltage status. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.15 |
| atsStatusHardwareStatus mandatory This variable returns the status of display board hardware. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.16 |
| atsStatus3dot3VPowerSupply mandatory This variable returns the present state of the ATS 3.3V supply.
atsPowerSupplyOK(2) indicates that the 3.3V power supply is operating
within tolerance, while atsPowerSupplyFailure… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.17 |
| atsStatus1Dot0VPowerSupply mandatory This variable returns the present state of the ATS 1.0V supply.
atsPowerSupplyOK(2) indicates that the 1.0V power supply is operating
within tolerance, while atsPowerSupplyFailure… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.18 |
| atsStatusVBoostSourceA mandatory This variable returns the present state of the ATS Source A Boost 48V supply.
atsPowerSupplyOK(2) indicates that the Source A 48V power supply is operating
within tolerance, while… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.19 |
| atsStatusSelectedSource mandatory This variable returns the current source of power. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.2 |
| atsStatusVBoostSourceB mandatory This variable returns the present state of the ATS Source B Boost 48V supply.
atsPowerSupplyOK(2) indicates that the Source B 48V power supply is operating
within tolerance, while… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.20 |
| atsStatusFuseSourceA mandatory This variable returns the Souce A Fuse State.
atsFuseStatusClose(1) indicates that Source A Fuse is close(normal),
atsFuseStatusOpen(2) indicates that Source A Fuse is open. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.21 |
| atsStatusFuseSourceB mandatory This variable returns the Souce B Fuse State.
atsFuseStatusClose(1) indicates that Source B Fuse is close(normal),
atsFuseStatusOpen(2) indicates that Source B Fuse is open. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.22 |
| atsStatusRedundancyState mandatory This variable returns the current redundancy state of the ATS.
atsRedundancyLost(1) indicates that the ATS is unable to
switch over to the alternate power source if the current so… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.3 |
| atsStatusOverCurrentState mandatory This variable returns the output current state of the ATS.
atsOverCurrent(1) indicates that the ATS has exceeded the output
current threshold and will not allow a switch over to t… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.4 |
| atsStatus5VPowerSupply mandatory This variable returns the present state of the ATS 5V power supply.
atsPowerSupplyFailure(1) indicates the 5V power supply has failed
and that the ATS serial port Configuration Me… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.5 |
| atsStatus24VPowerSupply mandatory This variable returns the present state of the ATS 24V power supply for Source A.
atsPowerSupplyFailure(1) indicates the 24V power supply has failed
and the ATS is unable to switc… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.6 |
| atsStatus24VSourceBPowerSupply mandatory This variable returns the present state of the ATS 24V power supply for Source B.
atsPowerSupplyFailure(1) indicates the 24V power supply has failed
and the ATS is unable to switc… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.7 |
| atsStatusPlus12VPowerSupply mandatory This variable returns the present state of the ATS 12V power supply.
atsPowerSupplyFailure(1) indicates the 12V power supply has failed
and the ATS is unable to monitor the curren… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.8 |
| atsStatusMinus12VPowerSupply mandatory This variable returns the present state of the ATS -12V power supply.
atsPowerSupplyFailure(1) indicates the -12V power supply has failed
and the ATS is unable to monitor the curr… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.8.5.1.9 |