airIRRCGroupStatusActiveFlowControlStatus
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.13.3.2.1.1.9
Object
scalar
mandatory
Enumeration
Status of the active flow control system.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.13.3.2.1.1.9- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- airIRRCGroupStatus
- Siblings
- 8
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | under |
2 | okay |
3 | over |
4 | notApplicable |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| airIRRCGroupStatusCoolOutput mandatory Group coolant output in tenths of kW. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.3.2.1.1.1 |
| airIRRCGroupStatusCoolDemand mandatory Group coolant demand in tenths of kW. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.3.2.1.1.2 |
| airIRRCGroupStatusAirFlowUS mandatory Group air flow in cubic feet per minute. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.3.2.1.1.3 |
| airIRRCGroupStatusAirFlowMetric mandatory Group air flow in liters per second. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.3.2.1.1.4 |
| airIRRCGroupStatusMaxRackInletTempUS mandatory Group maximum rack inlet temperature in tenths of
degrees Fahrenheit. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.3.2.1.1.5 |
| airIRRCGroupStatusMaxRackInletTempMetric mandatory Group maximum rack inlet temperature in tenths of
degrees Celsius. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.3.2.1.1.6 |
| airIRRCGroupStatusMinRackInletTempUS mandatory Group minimum rack inlet temperature in tenths of
degrees Fahrenheit. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.3.2.1.1.7 |
| airIRRCGroupStatusMinRackInletTempMetric mandatory Group minimum rack inlet temperature in tenths of