airIRG2RDT2StatusRackInletTempMetric
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.13.4.5.2.1.7
Object
scalar
mandatory
Integer32
The unit rack inlet temperature in tenths of degrees Celsius.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.13.4.5.2.1.7- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- airIRG2RDT2Status
- Siblings
- 29
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| airIRG2RDT2StatusOperateMode mandatory The cooling unit operating mode. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.1 |
| airIRG2RDT2StatusReturnAirTempUS mandatory The unit return air temperature in tenths of
degrees Fahrenheit. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.10 |
| airIRG2RDT2StatusReturnAirTempMetric mandatory The unit return air temperature in tenths of
degrees Celsius. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.11 |
| airIRG2RDT2StatusSuctionTempUS mandatory The unit suction temperature in tenths of
degrees Fahrenheit. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.12 |
| airIRG2RDT2StatusSuctionTempMetric mandatory The unit suction temperature in tenths of
degrees Celsius. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.13 |
| airIRG2RDT2StatusSuperheatTempUS mandatory The unit superheat temperature in tenths of
degrees Fahrenheit. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.14 |
| airIRG2RDT2StatusSuperheatTempMetric mandatory The unit superheat temperature in tenths of
degrees Celsius. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.15 |
| airIRG2RDT2StatusFilterDPUS mandatory The unit air filter differential pressure in
hundredths of inches of water. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.16 |
| airIRG2RDT2StatusFilterDPMetric mandatory The unit air filter differential pressure in pascals (Pa). | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.17 |
| airIRG2RDT2StatusSuctionPressureUS mandatory Unit suction pressure in pounds per square inch (PSI). | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.18 |
| airIRG2RDT2StatusSuctionPressureMetric mandatory Unit suction pressure in kiloPascals (kPa). | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.19 |
| airIRG2RDT2StatusCoolOutput mandatory The unit cooling output in tenths of kilowatts (kW). | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.2 |
| airIRG2RDT2StatusDischargePressureUS mandatory Unit discharge pressure in pounds per square inch (PSI). | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.20 |
| airIRG2RDT2StatusDischargePressureMetric mandatory Unit discharge pressure in kiloPascals (kPa). | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.21 |
| airIRG2RDT2StatusEvaporatorFanSpeed mandatory The unit average evaporator fan speed in tenths of percent. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.22 |
| airIRG2RDT2StatusInputState mandatory The state of the input contact. | scalar | AirIRG2RDType2IOState | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.23 |
| airIRG2RDT2StatusOutputState mandatory The state of the output relay. | scalar | AirIRG2RDType2IOState | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.24 |
| airIRG2RDT2StatusOHEInputState mandatory The state of the outside heat exchanger(OHE) input contact. | scalar | AirIRG2RDType2IOState | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.25 |
| airIRG2RDT2StatusOHEOutputState mandatory The state of the outside heat exchanger(OHE) output relay. | scalar | AirIRG2RDType2IOState | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.26 |
| airIRG2RDT2StatusCompressor mandatory The state (off/on) of the compressor. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.27 |
| airIRG2RDT2StatusFluidValvePos mandatory The position of the fluid valve in percent. This OID is only valid
when airIRG2RDT2ConfigUnitType indicates fluidCooled(1). | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.28 |
| airIRG2RDT2StatusHotGasBypassValvePos mandatory The position of the hot gas bypass valve in hundredths of percent. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.29 |
| airIRG2RDT2StatusCoolDemand mandatory The unit cooling demand in tenths of kilowatts (kW). | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.3 |
| airIRG2RDT2StatusLeakSensor mandatory The state (no-leak/leak) of the leak sensor. | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.30 |
| airIRG2RDT2StatusAirFlowUS mandatory The unit air flow in cubic feet per minute. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.4 |
| airIRG2RDT2StatusAirFlowMetric mandatory The unit air flow in liters per second. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.5 |
| airIRG2RDT2StatusRackInletTempUS mandatory The unit rack inlet temperature in tenths of
degrees Fahrenheit. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.6 |
| airIRG2RDT2StatusSupplyAirTempUS mandatory The unit supply air temperature in tenths of
degrees Fahrenheit. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.8 |
| airIRG2RDT2StatusSupplyAirTempMetric mandatory The unit supply air temperature in tenths of
degrees Celsius. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.4.5.2.1.9 |