airFMSysReheatDeadbandC
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.13.1.4.8.5
Object
scalar
mandatory
r/w
Integer32
The temperature range that controls output when the selected control sensor temperature is below the setpoint. At the bottom of this range, the reheat mode outputs at 100%. The deadband does not apply to PID-controlled modes. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.