airFMSysInterstageDelay
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.13.1.4.5.7
Object
scalar
mandatory
r/w
Integer32
The DX interstage delay allows the first compressor's cooling to take effect before engaging the second compressor. This prevents the second compressor from cycling on and off excessively. Measured in seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.13.1.4.5.7- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- airFMSysCooling
- Siblings
- 22
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| airFMSysCompMinOnTime mandatory Set the minimum time the compressor continues to
operate after it is started. The delay protects the
compressor from damage. Caution: Reducing this delay
shortens compressor life.… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.1 |
| airFMSysCoolSetpointC mandatory The target value for the selected control sensor air
for this mode. It must be at least 1.0 C above the
reheat setpoint if a heater is installed. Measured
in tenths of degrees Ce… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.10 |
| airFMSysCoolSetpointF mandatory The target value for the selected control sensor air
for this mode. It must be at least 1.0 C above the
reheat setpoint if a heater is installed. Measured
in tenths of degrees Fa… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.11 |
| airFMSysCoolDeadbandC mandatory The temperature range that controls output when the
selected control sensor temperature is above the
setpoint. At the top of this range, the cool mode
outputs at 100%. The deadban… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.12 |
| airFMSysCoolDeadbandF mandatory The temperature range that controls output when the
selected control sensor temperature is above the
setpoint. At the top of this range, the cool mode
outputs at 100%. The deadban… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.13 |
| airFMSysCoolEconIsolFunction mandatory Set the Economizer Automatic Coolant Isolation valve
to enabled or disabled. This valve anticipates a
cooling demand and opens the coil fluid valve.
A value of notApplicable indic… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.4.5.14 |
| airFMSysSuctPresCompensation mandatory Set the Suction Pressure Compensation to enabled or
disabled. This function attempts to keep the suction
pressure from exceeding 95 psi.
A value of notApplicable indicates that th… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.4.5.15 |
| airFMSysCoilFluidActivThreshC mandatory The minimum coolant temperature required to use the
optional MultiCool or Economizer coil. Measured in
tenths of degrees Celsius.
A value of -2147483648 indicates that this OID d… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.16 |
| airFMSysCoilFluidActivThreshF mandatory The minimum coolant temperature required to use the
optional MultiCool or Economizer coil. Measured in
tenths of degrees Fahrenheit.
A value of -2147483648 indicates that this OI… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.17 |
| airFMSysCoilFluidActivDeadbandC mandatory The controller will disengage the MultiCool or
Economizer coil when the coolant temperature reaches
the coil fluid temperature activation threshold plus
the deadband. Measured in… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.18 |
| airFMSysCoilFluidActivDeadbandF mandatory The controller will disengage the MultiCool or
Economizer coil when the coolant temperature reaches
the coil fluid temperature activation threshold plus
the deadband. Measured in… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.19 |
| airFMSysCompMinOffTime mandatory Set the minimum time the compressor will remain off
after it ceases operation. The delay protects the
compressor from damage. Caution: Reducing this delay
shortens compressor life… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.2 |
| airFMSysCoolPIDMethod mandatory Set the multipliers that the PID algorithm will use
to calculate the cool output. Proportional,
Proportional + Integral, or Proportional + Integral
+ Derivative.
A value of notApp… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.4.5.20 |
| airFMSysCoolPIDGainP mandatory Set the proportional multiplier to correct for
differences between the selected control sensor
actual temperature and the setpoint. Measured in
%/C.
A value of -2147483648 indica… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.21 |
| airFMSysCoolPIDResetRateI mandatory Set the integral multiplier to correct for the
proportional offset. Measured in %/(C * min).
A value of -2147483648 indicates that this OID does
not apply to this device due to i… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.22 |
| airFMSysCoolPIDDerivativeD mandatory Set the derivative multiplier to counteract overshoot
and droop during changes in the room load. Measured
in %/(C / min).
A value of -2147483648 indicates that this OID does
not … | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.23 |
| airFMSysCompRotPeriod mandatory Set how often to perform compressor runtime
balancing. Measured in hours.
A value of -2147483648 indicates that this OID does
not apply to this device due to its configuration. | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.3 |
| airFMSysEconIsolVlvOpenDelay mandatory Set the delay between opening the Economizer Isolator
output relay and engaging the compressors. Measured
in seconds.
A value of -2147483648 indicates that this OID does
not appl… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.4 |
| airFMSysEconIsolVlvCloseDelay mandatory Set the delay between disengaging the compressor and
closing the Economizer Isolator output relay.
Measured in seconds.
A value of -2147483648 indicates that this OID does
not app… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.5 |
| airFMSysCndsrFluidVlvCloseDelay mandatory Set the time the condenser valve remains open after
the compressors disengage. Measured in seconds.
A value of -2147483648 indicates that this OID does
not apply to this device d… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.5.6 |
| airFMSysCoolState mandatory Set the mode to enabled or disabled. Disabled modes
will not operate, and you cannot make changes to
their settings while they are disabled.
A value of notApplicable indicates tha… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.4.5.8 |
| airFMSysCoolEssFunction mandatory Set the priority of the mode for alarms and events
with the nonessential stop behavior. Nonessential
modes are disabled during nonessential stop alarms
and events.
A value of notA… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.4.5.9 |