airFMSysHighSplyTempC
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.13.1.4.9.1
Object
scalar
mandatory
r/w
Integer32
The high temperature threshold for air blown into the room (supply). If the supply temperature exceeds the threshold, an alarm will occur. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.13.1.4.9.1- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- airFMSysThresholds
- Siblings
- 15
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| airFMSysHighCtrlTempF mandatory The high temperature threshold for air monitored by
the System. If the temperature exceeds the threshold,
an alarm will occur. Measured in tenths of degrees
Fahrenheit.
A value o… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.10 |
| airFMSysLowCtrlTempC mandatory The low temperature threshold for air monitored by
the System. If the temperature drops below the
threshold, an alarm will occur. Measured in tenths
of degrees Celsius.
A value o… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.11 |
| airFMSysLowCtrlTempF mandatory The low temperature threshold for air monitored by
the System. If the temperature drops below the
threshold, an alarm will occur. Measured in tenths
of degrees Fahrenheit.
A valu… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.12 |
| airFMSysHighCtrlHum mandatory The high humidity threshold for air monitored by the
System. If the humidity exceeds the threshold, an
alarm will occur. Measured in tenths of percent
relative humidity.
A value … | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.13 |
| airFMSysLowCtrlHum mandatory The low humidity threshold for air monitored by the
System. If the humidity drops below the threshold,
an alarm will occur. Measured in tenths of percent
relative humidity.
A val… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.14 |
| airFMSysTempAlarmDelay mandatory The amount of time the blower must be on before a
temperature alarm can be issued. Measured in
seconds.
A value of -2147483648 indicates that this OID does
not apply to this devi… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.15 |
| airFMSysHumAlarmDelay mandatory The amount of time the blower must be on before a
humidity alarm can be issued. Measured in seconds.
A value of -2147483648 indicates that this OID does
not apply to this device … | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.16 |
| airFMSysHighSplyTempF mandatory The high temperature threshold for air blown into the
room (supply). If the supply temperature exceeds the
threshold, an alarm will occur. Measured in tenths
of degrees Fahrenhei… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.2 |
| airFMSysLowSplyTempC mandatory The low temperature threshold for air blown into the
room (supply). If the supply temperature drops below
the threshold, an alarm will occur. Measured in
tenths of degrees Celsiu… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.3 |
| airFMSysLowSplyTempF mandatory The low temperature threshold for air blown into the
room (supply). If the supply temperature drops below
the threshold, an alarm will occur. Measured in
tenths of degrees Fahrenh… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.4 |
| airFMSysHighCoilFluidTempC mandatory The high temperature threshold for coolant at the
inlet to the fluid coil. If the fluid coil coolant
temperature exceeds the threshold, an alarm will
occur. Measured in tenths of… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.5 |
| airFMSysHighCoilFluidTempF mandatory The high temperature threshold for coolant at the
inlet to the fluid coil. If the fluid coil coolant
temperature exceeds the threshold, an alarm will
occur. Measured in tenths of… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.6 |
| airFMSysLowCoilFluidTempC mandatory The low temperature threshold for coolant at the
inlet to the fluid coil. If the fluid coil coolant
temperature drops below the threshold, an alarm will
occur. Measured in tenths… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.7 |
| airFMSysLowCoilFluidTempF mandatory The low temperature threshold for coolant at the
inlet to the fluid coil. If the fluid coil coolant
temperature drops below the threshold, an alarm will
occur. Measured in tenths… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.8 |
| airFMSysHighCtrlTempC mandatory The high temperature threshold for air monitored by
the System. If the temperature exceeds the threshold,
an alarm will occur. Measured in tenths of degrees
Celsius.
A value of -… | scalar | Integer32 | .1.3.6.1.4.1.318.1.1.13.1.4.9.9 |