airFMGroupFailoverModAirBlockInterlockOpen
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.13.1.3.7.2.11
Object
scalar
mandatory
r/w
Enumeration
Enabling this OID will cause the system to enter a failure state if the air block interlock is open on a module. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.13.1.3.7.2.11- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- airFMGroupFailoverMod
- Siblings
- 12
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | notApplicable |
2 | disable |
3 | enable |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| airFMGroupFailoverModMaintRequired mandatory Enabling this OID will cause the system to enter
a failure state if maintenance is required on a
module.
Once in the failure state, environmental control
ceases for the system, an… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.3.7.2.1 |
| airFMGroupFailoverModHumReplaceCylinder mandatory Enabling this OID will cause the system to enter
a failure state if a humidifier needs its cylinder
replaced on a module.
Once in the failure state, environmental control
ceases f… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.3.7.2.10 |
| airFMGroupFailoverModWaterDetected mandatory Enabling this OID will cause the system to enter
a failure state if water is detected by a module.
Once in the failure state, environmental control
ceases for the system, and the … | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.3.7.2.12 |
| airFMGroupFailoverModCondensatePumpFail mandatory Enabling this OID will cause the system to enter
a failure state if the condensate pump has failed in
a module.
Once in the failure state, environmental control
ceases for the sys… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.3.7.2.13 |
| airFMGroupFailoverModCoolFail mandatory Enabling this OID will cause the system to enter
a failure state if cooling has failed on a module.
Once in the failure state, environmental control
ceases for the system, and the… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.3.7.2.2 |
| airFMGroupFailoverModHumFail mandatory Enabling this OID will cause the system to enter
a failure state if the humidifier has failed on a
module.
Once in the failure state, environmental control
ceases for the system, … | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.3.7.2.3 |
| airFMGroupFailoverModBlwrCntrl1Fail mandatory Enabling this OID will cause the system to enter
a failure state if blower controller 1 has failed on
a module.
Once in the failure state, environmental control
ceases for the sys… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.3.7.2.4 |
| airFMGroupFailoverModBlwrCntrl2Fail mandatory Enabling this OID will cause the system to enter
a failure state if blower controller 2 has failed on
a module.
Once in the failure state, environmental control
ceases for the sys… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.3.7.2.5 |
| airFMGroupFailoverModHighFilterDP mandatory Enabling this OID will cause the system to enter
a failure state if a high filter differential
pressure is present on a module.
Once in the failure state, environmental control
ce… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.3.7.2.6 |
| airFMGroupFailoverModHighSupplyTemp mandatory Enabling this OID will cause the system to enter
a failure state if a high supply temperature is
active on a module.
Once in the failure state, environmental control
ceases for th… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.3.7.2.7 |
| airFMGroupFailoverModLowSupplyTemp mandatory Enabling this OID will cause the system to enter
a failure state if a low supply temperature is active
on a module.
Once in the failure state, environmental control
ceases for the… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.3.7.2.8 |
| airFMGroupFailoverModLossOrLowAirFlow mandatory Enabling this OID will cause the system to enter
a failure state if there is a loss of air flow or low
air flow on a module.
Once in the failure state, environmental control
cease… | scalar | Enumeration | .1.3.6.1.4.1.318.1.1.13.1.3.7.2.9 |