rPDU2RCMAlarmStatus
PowerNet-Inova ·
.1.3.6.1.4.1.63131.1.1.26.15.1.1.4
Object
column
mandatory
r/w
Enumeration
RCM alarm status. Setting the selected variable to 1, will clear the over alarm.
Context
- MIB
- PowerNet-Inova
- OID
.1.3.6.1.4.1.63131.1.1.26.15.1.1.4- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- rPDU2RCMEntry
- Table
- rPDU2RCMTable
- Siblings
- 7
Syntax
Enumeration
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDU2RCMIndex mandatory The index to the Rack PDU RCM table entry | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.15.1.1.1 |
| rPDU2RCMModule mandatory The user-defined Rack PDU numeric ID | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.15.1.1.2 |
| rPDU2RCMCurrent mandatory RCM RMS current. (mA) | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.15.1.1.3 |
| rPDU2RCMSelfCheckCommand mandatory Getting this variable will return the RCM self checking status,
1: featureNotAvailable(-1) 2: success(1) 3: failed(2) 4: pending(3).
Setting any of the selected pdu's rcm's varia… | column | Enumeration | .1.3.6.1.4.1.63131.1.1.26.15.1.1.5 |
| rPDU2RCMWarningThreshold mandatory Over Warning threshold of RCM current. (mA),
threshold can be set in the range of 15-300mA,
and must be lower or equal than Alarm threshold. | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.15.1.1.6 |
| rPDU2RCMAlarmThreshold mandatory Over Alarm threshold of RCM current. (mA),
threshold can be set in the range of 15~300 mA,
and must be higher or equal than Warning threshold. | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.15.1.1.7 |
| rPDU2RCMSelfCheckPeriod mandatory RCM Self-Checking Period. (day)
period can be set in the range of 1~365 days,
the rcm period on a single pdu is the same,
setting one of the selected pdu's rcm's period,
will chan… | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.15.1.1.8 |