rPDU2DevicePropertiesOutletLayout
PowerNet-Inova ·
.1.3.6.1.4.1.63131.1.1.26.4.2.1.11
Object
column
mandatory
Enumeration
Getting this OID will return outlet layout for the device.
seqPhaseToNeutral(1) indicates outlet layout as follows:
1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,...
or for single phase SKUs, all outlets 1-N
seqPhaseToPhase(2) indicates outlet layout as follows:
1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,...
seqPhToNeu21PhToPh(3) indicates outlet layout as follows:
1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,...
seqPhToPhGrouped(4) indicates outlet layout as follows:
For AP8xxx SKU's Group 1:1-2, Group 2:2-3, Group 3:3-1.
seqPhToNGrouped(5) indicates outlet layout as follows:
This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N.
seqPToN1516PToPGrouped(6) indicates outlet layout as follows:
This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2,
Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1.
seqPhToPh2xGrouped(7) indicates outlet layout as follows:
This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3,
Group 4:2-3, Group 5:3-1, Group 6:3-1.
seqPhToN2xGrouped(8) indicates outlet layout as follows:
This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N,
Group 4:2-N, Group 5:3-N, Group 6:3-N.
seqNotApplicable(9):
Outlet layout does not affect any of the user interfaces for
AP88XX SKUs. These SKUs may report seqNotApplicable(9) if there is
not an exact outlet layout match available.
seqPhToNPhToPhPhToN(10) indicates outlet layout as follows:
Group 1:1-N, Group 2:1-2, Group 3:2-N.
Only AP7xxx, AP8xxx SKUs support this feature. Product which does not
support this feature will respond with -1
Context
- MIB
- PowerNet-Inova
- OID
.1.3.6.1.4.1.63131.1.1.26.4.2.1.11- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- rPDU2DevicePropertiesEntry
- Table
- rPDU2DevicePropertiesTable
- Siblings
- 12
Syntax
Enumeration
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| rPDU2DevicePropertiesIndex mandatory The index to the Rack PDU properties table entry | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.4.2.1.1 |
| rPDU2DevicePropertiesOrientation mandatory Rack PDU orientation | column | Enumeration | .1.3.6.1.4.1.63131.1.1.26.4.2.1.10 |
| rPDU2DevicePropertiesMaxPhaseCurrentRating mandatory The maximum current rating, measured in Amps, for
the Rack PDU | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.4.2.1.12 |
| rPDU2DevicePropertiesDevicePowerRating mandatory The maximum power rating, measured in tenths of kilowatts, for
the Rack PDU | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.4.2.1.13 |
| rPDU2DevicePropertiesModule mandatory The user-defined Rack PDU numeric ID | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.4.2.1.2 |
| rPDU2DevicePropertiesName mandatory A user-defined string identifying the Rack PDU | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.63131.1.1.26.4.2.1.3 |
| rPDU2DevicePropertiesNumOutlets mandatory The number of outlets on the Rack PDU | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.4.2.1.4 |
| rPDU2DevicePropertiesNumSwitchedOutlets mandatory The number of switched outlets on the Rack PDU | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.4.2.1.5 |
| rPDU2DevicePropertiesNumMeteredOutlets mandatory The number of metered outlets on the Rack PDU | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.4.2.1.6 |
| rPDU2DevicePropertiesNumPhases mandatory The number of phases present in the Rack PDU | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.4.2.1.7 |
| rPDU2DevicePropertiesNumMeteredBanks mandatory The number of metered banks present in the Rack PDU | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.4.2.1.8 |
| rPDU2DevicePropertiesMaxCurrentRating mandatory The maximum current rating, measured in Amps, for
the Rack PDU | column | Integer32 | .1.3.6.1.4.1.63131.1.1.26.4.2.1.9 |