rPDU2DeviceControlCommand

PowerNet-Inova · .1.3.6.1.4.1.63131.1.1.26.4.4.1.4

Object

column mandatory r/w Enumeration
Setting this OID to immediateAllOn (1) will turn all outlets
on immediately.
              
Setting this OID to delayedAllOn (2) will turn all outlets on as
defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime
OID value.
              
Setting this OID to immediateAllOff (3) will turn all outlets
off immediately.
              
Setting this OID to immediateAllReboot (4) will cause an immediateAllOff
command to be performed. Once all outlets are off, the
Switched Rack PDU will then delay the
rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform an
immediateAllOn command.
              
Setting this OID to delayedAllReboot (5) will cause a
delayedAllOff command to be performed. Once all outlets are off,
the Switched Rack PDU will then delay the largest
rPDU2OutletSwitchedConfigRebootDuration OID time, and then perform a
delayedAllOn command.
              
Setting this OID to noCommandAll (6) will have no effect.
              
Setting this OID to delayedAllOff (7) will turn all outlets off
as defined by each outlet's rPDU2OutletSwitchedConfigPowerOffTime
OID value.
              
Setting this OID to cancelAllPendingCommands (8) will cause all pending
commands on the Switched Rack PDU to be cancelled.
              
Getting this OID will return the noCommandAll (6)
value.

Context

MIB
PowerNet-Inova
OID
.1.3.6.1.4.1.63131.1.1.26.4.4.1.4
Type
column
Access
readwrite
Status
mandatory
Parent
rPDU2DeviceControlEntry
Table
rPDU2DeviceControlTable
Siblings
3

Syntax

Enumeration

Values & Constraints

No enumerated values or constraints recorded.

Related Objects

Sibling Objects