pmPowerMgmtPDUTableVoltageMin
PM-MIB ·
.1.3.6.1.4.1.10418.17.2.5.3.1.72
Object
column
SNMPv2-SMIInteger32
Minimum value of voltage in the PDU (V). Returns 0 if not supported.
Context
- MIB
- PM-MIB
- OID
.1.3.6.1.4.1.10418.17.2.5.3.1.72- Type
- column
- Access
- readonly
- Status
- current
- Parent
- pmPowerMgmtPDUTableEntry
- Table
- pmPowerMgmtPDUTable
- Siblings
- 75
Syntax
SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pmPowerMgmtPDUTablePortNumber Number of serial port when the PDU is connected. | column | IF-MIBInterfaceIndex | .1.3.6.1.4.1.10418.17.2.5.3.1.1 |
| pmPowerMgmtPDUTableCurrent1Value obsolete Current of the sensor 1 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.10 |
| pmPowerMgmtPDUTableCurrentHighCritical outlet high critical (alarm) current threshold (A x 10).
Set fails if value is lower that CurrentHighWarning.
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.100 |
| pmPowerMgmtPDUTableCurrentHighWarning outlet high warning current threshold (A x 10).
Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning.
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.101 |
| pmPowerMgmtPDUTableCurrentLowWarning outlet low warning current threshold (A x 10).
Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical.
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.102 |
| pmPowerMgmtPDUTableCurrentLowCritical outlet low critical current threshold (A x 10).
Set fails if value is higher than CurrentLowWarning.
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.103 |
| pmPowerMgmtPDUTableEnergyValue pdu energy value (Wh).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.105 |
| pmPowerMgmtPDUTableEnergyStartTime time at which energy calculation commenced (ISO8601 format).
Returns N/A if not applicable. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.17.2.5.3.1.106 |
| pmPowerMgmtPDUTableEnergyReset noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU. | column | Enumeration | .1.3.6.1.4.1.10418.17.2.5.3.1.107 |
| pmPowerMgmtPDUTableCurrent1Max obsolete Maximum current of the sensor 1 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.11 |
| pmPowerMgmtPDUTableCurrent2Value obsolete Current of the sensor 2 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.12 |
| pmPowerMgmtPDUTableCurrent2Max obsolete Maximum current of the sensor 2 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.13 |
| pmPowerMgmtPDUTableCurrent3Value obsolete Current of the sensor 3 in this PDU unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.14 |
| pmPowerMgmtPDUTableCurrent3Max obsolete Maximum current of the sensor 3 in this PDU unit in AMP.
When the PDU does not have support for maximum value,
the value will be 0.
The value of this object is the actual current … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.15 |
| pmPowerMgmtPDUTableTemperatureNOS obsolete Number of temperature sensors in the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.16 |
| pmPowerMgmtPDUTableTemperature1Value obsolete Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.17 |
| pmPowerMgmtPDUTableTemperature1Max obsolete Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actu… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.18 |
| pmPowerMgmtPDUTableTemperature2Value obsolete Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.19 |
| pmPowerMgmtPDUTablePduIndex A PDU position in the chain. | column | IF-MIBInterfaceIndexOrZero | .1.3.6.1.4.1.10418.17.2.5.3.1.2 |
| pmPowerMgmtPDUTableTemperature2Max obsolete Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actua… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.20 |
| pmPowerMgmtPDUTableTemperature3Value obsolete Temperature of this PM unit in Celsius degrees.
The value of this object is the actual temperature in
degrees C * 10. You need to translate the readed value
(Ex. : value is 240, … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.21 |
| pmPowerMgmtPDUTableTemperature3Max obsolete Maximum temperature detected in this PM unit in Celsius degrees.
The value will be Zero when the PDU does not have support for maximum value.
The value of this object is the actu… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.22 |
| pmPowerMgmtPDUTableHumidityNOS obsolete Number of humidity sensors in the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.23 |
| pmPowerMgmtPDUTableHumidity1Value obsolete Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.24 |
| pmPowerMgmtPDUTableHumidity1Max obsolete Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero v… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.25 |
| pmPowerMgmtPDUTableHumidity2Value obsolete Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.26 |
| pmPowerMgmtPDUTableHumidity2Max obsolete Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero v… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.27 |
| pmPowerMgmtPDUTableHumidity3Value obsolete Humidity of this PM unit .
If the humidity measurement is not installed this
value will be 0. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.28 |
| pmPowerMgmtPDUTableHumidity3Max obsolete Maximum humidity detected in this PM unit.
If the humidity measurement is not installed or the PDU does not have support for maximum value this
value will be 0.
Set with Zero v… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.29 |
| pmPowerMgmtPDUTablePduId PDU identification. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.17.2.5.3.1.3 |
| pmPowerMgmtPDUTableVoltageNOS obsolete Number of voltage sensors in the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.30 |
| pmPowerMgmtPDUTableVoltage1Value obsolete Voltage of this sensor in this PDU unit.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageValue,
pmPowerMgmtPhasesTableVoltageValue, or
pmPowerM… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.31 |
| pmPowerMgmtPDUTableVoltage1Max obsolete Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVolta… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.32 |
| pmPowerMgmtPDUTableVoltage2Value obsolete Voltage of this sensor in this PDU unit.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageValue,
pmPowerMgmtPhasesTableVoltageValue, or
pmPowerM… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.33 |
| pmPowerMgmtPDUTableVoltage2Max obsolete Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVolta… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.34 |
| pmPowerMgmtPDUTableVoltage3Value obsolete Voltage of this sensor in this PDU unit.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVoltageValue,
pmPowerMgmtPhasesTableVoltageValue, or
pmPowerM… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.35 |
| pmPowerMgmtPDUTableVoltage3Max obsolete Maximum voltage of this sensor in this PDU unit.
Set with Zero value to clear the maximum voltage.
This OID is obsoleted. The value can be retrieved
from pmPowerMgmtPDUTableVolta… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.36 |
| pmPowerMgmtPDUTableNumberOfPhases Number of phases of the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.37 |
| pmPowerMgmtPDUTableNumberOfBanks Number of banks in the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.38 |
| pmPowerMgmtPDUTablePortName Name of serial port when the PDU is connected. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.17.2.5.3.1.4 |
| pmPowerMgmtPDUTableNumberOfSensors Number of sensors in the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.40 |
| pmPowerMgmtPDUTableFactoryDefault A set value of 2 will set the PDU to factory default settings.
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the factory default command is sen… | column | Enumeration | .1.3.6.1.4.1.10418.17.2.5.3.1.41 |
| pmPowerMgmtPDUTableColdStartDelay PDUs cold start delay in whole seconds (0-60).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.42 |
| pmPowerMgmtPDUTableReboot A set value of power*(2) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
reboot(2) = when SET the reboot command is sent to PDU. | column | Enumeration | .1.3.6.1.4.1.10418.17.2.5.3.1.43 |
| pmPowerMgmtPDUTableMaxCurrent Maximum value of current allowed in the PDU (A x 10). | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.44 |
| pmPowerMgmtPDUTableAlarm Show the PDU alarm status.
Returns 0 if not supported. | column | Enumeration | .1.3.6.1.4.1.10418.17.2.5.3.1.45 |
| pmPowerMgmtPDUTableModel Model of the PDU.
Returns N/A if not applicable. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.17.2.5.3.1.5 |
| pmPowerMgmtPDUTableCurrentValue Actual value of current in the PDU (A x 10).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.50 |
| pmPowerMgmtPDUTableCurrentMax Maximum value of current in the PDU (A x 10).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.51 |
| pmPowerMgmtPDUTableCurrentMin Minimum value of current in the PDU (A x 10).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.52 |
| pmPowerMgmtPDUTableCurrentAvg Average value of current in the PDU (A x 10).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.53 |
| pmPowerMgmtPDUTableCurrentReset noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU. | column | Enumeration | .1.3.6.1.4.1.10418.17.2.5.3.1.54 |
| pmPowerMgmtPDUTableVendor Vendor of the PDU.
Returns N/A if not applicable. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.17.2.5.3.1.6 |
| pmPowerMgmtPDUTablePowerValue Actual value of power in the PDU (W x 10).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.60 |
| pmPowerMgmtPDUTablePowerMax Maximum value of power in the PDU (W x 10).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.61 |
| pmPowerMgmtPDUTablePowerMin Minimum value of power in the PDU (W x 10).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.62 |
| pmPowerMgmtPDUTablePowerAvg Average value of power in the PDU (W x 10).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.63 |
| pmPowerMgmtPDUTablePowerReset noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU. | column | Enumeration | .1.3.6.1.4.1.10418.17.2.5.3.1.64 |
| pmPowerMgmtPDUTablePowerType Type of power values.
Returns 0 if not supported. | column | Enumeration | .1.3.6.1.4.1.10418.17.2.5.3.1.65 |
| pmPowerMgmtPDUTableFirmwareVersion Version of the PDU firmware.
Returns N/A if not applicable. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.10418.17.2.5.3.1.7 |
| pmPowerMgmtPDUTableVoltageValue Actual value of voltage in the PDU (V).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.70 |
| pmPowerMgmtPDUTableVoltageMax Maximum value of voltage in the PDU (V).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.71 |
| pmPowerMgmtPDUTableVoltageAvg Average value of voltage in the PDU (V).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.73 |
| pmPowerMgmtPDUTableVoltageReset noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU. | column | Enumeration | .1.3.6.1.4.1.10418.17.2.5.3.1.74 |
| pmPowerMgmtPDUTableVoltageType Type of voltage values.
Returns 0 if not supported. | column | Enumeration | .1.3.6.1.4.1.10418.17.2.5.3.1.75 |
| pmPowerMgmtPDUTableNumberOfOutlets Number of outlets of the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.8 |
| pmPowerMgmtPDUTablePowerFactorValue Actual value of power factor in the PDU (Pf x 100).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.80 |
| pmPowerMgmtPDUTablePowerFactorMax Maximum value of power factor in the PDU (Pf x 100).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.81 |
| pmPowerMgmtPDUTablePowerFactorMin Minimum value of power factor in the PDU (Pf x 100).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.82 |
| pmPowerMgmtPDUTablePowerFactorAvg Average value of power factor in the PDU (Pf x 100).
Returns 0 if not supported. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.83 |
| pmPowerMgmtPDUTablePowerFactorReset noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU. | column | Enumeration | .1.3.6.1.4.1.10418.17.2.5.3.1.84 |
| pmPowerMgmtPDUTablePowerFactorType Type of power values.
Returns 0 if not supported. | column | Enumeration | .1.3.6.1.4.1.10418.17.2.5.3.1.85 |
| pmPowerMgmtPDUTableCurrentNOS obsolete Number of current sensors in the PDU. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.10418.17.2.5.3.1.9 |
| pmPowerMgmtPDUTablePowerControl A set value of power*(2-4) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
powerOn(2) = when SET the power On command is sent to PDU.
power… | column | Enumeration | .1.3.6.1.4.1.10418.17.2.5.3.1.90 |
| pmPowerMgmtPDUTableResetOCP A set value of power*(2) will send command to PDU.
noAction(1) = always returned in a GET. Does nothing if SET.
reset(2) = when SET the reset command is sent to PDU.
Returns 0 if… | column | Enumeration | .1.3.6.1.4.1.10418.17.2.5.3.1.91 |