pdug5OutletControlPowerOnState
PANDUIT-MIB ·
.1.3.6.1.4.1.19536.10.1.5.2.1.5
Object
column
r/w
Enumeration
Determines the outlet state when power is applied to the unit. 1 : not restart at device startup 2 : should sequence back ON in line with outletControlSequenceTime 3 : should take the state the outlet had when power was lost. If the state was ON, should sequence back ON in line with outletControlSequenceTime.
Context
- MIB
- PANDUIT-MIB
- OID
.1.3.6.1.4.1.19536.10.1.5.2.1.5- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- pdug5OutletControlEntry
- Table
- pdug5OutletControlTable
- Siblings
- 9
Syntax
Enumeration
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pdug5OutletControlStatus current state of a control outlet. | column | Enumeration | .1.3.6.1.4.1.19536.10.1.5.2.1.1 |
| pdug5OutletControlCommand Getting this variable will return the outlet state.
If the outlet is on, the immediateOn (2)
value will be returned. If the outlet is off,
the immediateOff (1) value will be retur… | column | Enumeration | .1.3.6.1.4.1.19536.10.1.5.2.1.10 |
| pdug5OutletControlOffCmd When write, once issued, the outlet will turn Off immediately.
0-n: Time in seconds until the outlet command is issued
-1: Cancel a pending outlet Off command
When read, returns -… | column | Integer32 | .1.3.6.1.4.1.19536.10.1.5.2.1.2 |
| pdug5OutletControlOnCmd When write, once issued, the outlet will turn On immediately.
0-n: Time in seconds until the outlet command is issued
-1: Cancel a pending outlet On command
When read, returns -1 … | column | Integer32 | .1.3.6.1.4.1.19536.10.1.5.2.1.3 |
| pdug5OutletControlRebootCmd When write, for outlets that are On prior to this Reboot command, they will
switch Off immediately when the command is issued, remain Off for
outletControlRebootOffTime seconds, a… | column | Integer32 | .1.3.6.1.4.1.19536.10.1.5.2.1.4 |
| pdug5OutletControlSequenceDelay Time delay in seconds from when a Global Sequence On command is issued to when
the command is executed on this outlet. This delay is also used as a power-on delay. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.5.2.1.6 |
| pdug5OutletControlRebootOffTime Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.5.2.1.7 |
| pdug5OutletControlSwitchable Determines the outlet capability to be controlled On/Off from the communication channels.
1 : control On/Off enabled
2 : control On/Off disabled. | column | Enumeration | .1.3.6.1.4.1.19536.10.1.5.2.1.8 |
| pdug5OutletControlShutoffDelay Time delay in seconds that could be taken in account before shutting of the outlet.
An application which need to shutoff properly an outlet will read this parameter first
then wri… | column | Integer32 | .1.3.6.1.4.1.19536.10.1.5.2.1.9 |