pdug5InputRcmThResetThld
PANDUIT-MIB ·
.1.3.6.1.4.1.19536.10.1.2.3.1.5
Object
column
r/w
Integer32
The Reset threshold is the number of amps the reading needs to fall below the threshold setting for the condition to be cleared. Units are 0.01 amps.
Context
- MIB
- PANDUIT-MIB
- OID
.1.3.6.1.4.1.19536.10.1.2.3.1.5- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- pdug5InputRcmEntry
- Table
- pdug5InputRcmTable
- Siblings
- 8
Syntax
Integer32
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pdug5InputRcmEnabled RCM configuration value
off(0) if the PDU doesn't have RCM,
on(1) if the PDU has RCM. | column | Enumeration | .1.3.6.1.4.1.19536.10.1.2.3.1.1 |
| pdug5InputRcmModStatus RCM module status
ok(2) if the PDU can communicate with the RCM module,
failed(4) if the PDU cannot communicate with the RCM module,
degraded(3) if the PDU can communicate with th… | column | Enumeration | .1.3.6.1.4.1.19536.10.1.2.3.1.2 |
| pdug5InputRcmThUpperWarning RCM Current Upper warning threshold. Units are 0.01 amps.
A negative value indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.3.1.3 |
| pdug5InputRcmThUpperCritical RCM Current Upper critical threshold. Units are 0.01 amps.
A negative value indicates that this object is not available. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.3.1.4 |
| pdug5InputRcmThChangeDelay The number of consecutive sample that the condition is present before
an alarm is raised. | column | Integer32 | .1.3.6.1.4.1.19536.10.1.2.3.1.6 |
| pdug5InputRcmThCtrl Rcm current alarm threshold control:
0 - Enable UC and UW
1 - Disable UC and Enable UW
2 - Enable UC and Disable UW
3 - Disable UC and UW
4 and above - Bad input | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.3.1.7 |
| pdug5InputRcmThStatus Status of the measured Rcm current relative to the configured thresholds. | column | Enumeration | .1.3.6.1.4.1.19536.10.1.2.3.1.8 |
| pdug5InputRcmCurrent Rcm module current reading. Units are milliAmps. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.19536.10.1.2.3.1.9 |