dcLoadCurrent
ORION-BASE-MIB ·
.1.3.6.1.4.1.20246.2.3.1.1.1.2.3.2
Object
The measured load current. The max. value 2147483647 is used to indicate an invalid value.
Context
- MIB
- ORION-BASE-MIB
- OID
.1.3.6.1.4.1.20246.2.3.1.1.1.2.3.2- Type
- scalar
- Access
- readonly
- Status
- current
- Units
- 100 mA
- Parent
- dcSystemMonitor
- Siblings
- 7
Syntax
100 mA SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| dcSystemVoltage The measured system voltage. The max. value 2147483647
is used to indicate an invalid value. | scalar | 10 mV SNMPv2-SMIInteger32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.3.1 |
| dcBatteryCurrent The measured battery current. The max. value 2147483647
is used to indicate an invalid value. | scalar | 100 mA SNMPv2-SMIInteger32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.3.3 |
| dcBatteryTemperature The measured battery temperature. The max. value 2147483647
is used to indicate an invalid value. | scalar | 0.1 degree SNMPv2-SMIInteger32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.3.4 |
| dcChargeState Battery charge state. | scalar | Enumeration | .1.3.6.1.4.1.20246.2.3.1.1.1.2.3.5 |
| dcCurrentLimit Battery current limit. | scalar | Enumeration | .1.3.6.1.4.1.20246.2.3.1.1.1.2.3.6 |
| dcRectifierCurrent Total current of all working rectifier modules.
The maximum value 2147483647 is used to indicate
an invalid value. | scalar | 100 mA SNMPv2-SMIInteger32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.3.7 |
| dcSystemPower Calculated system power. The maximum value
2147483647 is used to indicate an invalid value. | scalar | 1 W SNMPv2-SMIInteger32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.3.8 |