dcEnableUsTempComp
ORION-BASE-MIB ·
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.9
Object
scalar
r/w
Enumeration
Checkbox to enable the automatic temperature compensation for the Us thresholds (Us min, Us max).
Context
- MIB
- ORION-BASE-MIB
- OID
.1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.9- Type
- scalar
- Access
- readwrite
- Status
- current
- Parent
- dcSystemVoltageSupervision
- Siblings
- 8
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | no |
2 | yes |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| dcUaMax If the system voltage is outside the range specified by the values
UaMin (lower alarm voltage)/UaMax (upper alarm voltage), the
system event 'S Ua low'/'S Ua high' is activated.… | scalar | 10 mV SNMPv2-SMIInteger32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.1 |
| dcUaMin For details see dcUaMax. | scalar | 10 mV SNMPv2-SMIInteger32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.2 |
| dcUsMax If the voltage is outside the range defined by the parameters UsMin (lower
safety voltage)/UsMax (upper safety voltage), the system event
'S Us low'/'S Us high' is activated. If… | scalar | 10 mV SNMPv2-SMIInteger32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.3 |
| dcUsMin For details see dcUsMax. | scalar | 10 mV SNMPv2-SMIInteger32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.4 |
| dcBoD Voltage threshold for Battery on Discharge alarm. | scalar | 10 mV SNMPv2-SMIInteger32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.5 |
| dcHysteresis Hysteresis used for Ua and Us. | scalar | 10 mV SNMPv2-SMIInteger32 | .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.6 |
| dcSuppressUaLowEnabled Suppress Ua Low alarm during mains failure. | scalar | Enumeration | .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.7 |
| dcSuppressUsLowEnabled Suppress Us Low alarm during mains failure. | scalar | Enumeration | .1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.8 |