upsStartupAfterDelay

MITSUBISHI-UPS-MIB · .0.13891.101.8.3

Object

scalar mandatory r/w Integer32
Setting this object will start the output after the
indicated number of seconds, including starting the
UPS, if necessary.  Setting this object to 0 will
cause the startup to occur immediately.  Setting this
object to -1 will abort the countdown.  If the output
is already on at the time the countdown reaches 0,
then nothing will happen.  Sets to this object
override the effect of any upsStartupAfterDelay
countdown or upsRebootWithDuration countdown in
progress.  When read, upsStartupAfterDelay will return
the number of seconds until startup, or -1 if no
startup countdown is in effect.  If the countdown
expires during a utility failure, the startup shall
not occur until the utility power is restored.  On
some systems, if the agent is restarted while a
startup countdown is in effect, the countdown is
aborted.

Context

MIB
MITSUBISHI-UPS-MIB
OID
.0.13891.101.8.3
Type
scalar
Access
readwrite
Status
mandatory
Parent
upsControl
Siblings
4

Syntax

Integer32
Source
COPS-PR-SPPIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647

Related Objects

Sibling Objects