upsRebootWithDuration
MITSUBISHI-UPS-MIB ·
.0.13891.101.8.4
Object
scalar
mandatory
r/w
Integer32
Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.
Context
- MIB
- MITSUBISHI-UPS-MIB
- OID
.0.13891.101.8.4- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsControl
- Siblings
- 4
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsShutdownType mandatory This object determines the nature of the action to be
taken at the time when the countdown of the
upsShutdownAfterDelay and upsRebootWithDuration
objects reaches zero.
… | scalar | Enumeration | .0.13891.101.8.1 |
| upsShutdownAfterDelay mandatory Setting this object will shutdown (i.e., turn off)
either the UPS output or the UPS system (as determined
by the value of upsShutdownType at the time of
shutdown) after the indica… | scalar | Integer32 | .0.13891.101.8.2 |
| upsStartupAfterDelay mandatory Setting this object will start the output after the
indicated number of seconds, including starting the
UPS, if necessary. Setting this object to 0 will
cause the startup to occu… | scalar | Integer32 | .0.13891.101.8.3 |
| upsAutoRestart mandatory Setting this object to 'on' will cause the UPS system
to restart after a shutdown if the shutdown occurred
during a power loss as a result of either a