upsConfigAudibleStatus
MITSUBISHI-UPS-MIB ·
.0.13891.101.9.8
Object
scalar
mandatory
r/w
Enumeration
The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.
Context
- MIB
- MITSUBISHI-UPS-MIB
- OID
.0.13891.101.9.8- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsConfig
- Siblings
- 9
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | disabled |
2 | enabled |
3 | muted |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsConfigInputVoltage mandatory The magnitude of the nominal input voltage (RMS Volts).
On those systems which support read-write access to this
object, if there is an attempt to set this variable to
a value t… | scalar | NonNegativeInteger | .0.13891.101.9.1 |
| upsConfigHighVoltageTransferPoint mandatory The maximum line voltage (RMS Volts) allowed before the UPS
system transfers to battery backup. | scalar | NonNegativeInteger | .0.13891.101.9.10 |
| upsConfigInputFreq mandatory The nominal input frequency (0.1 Hertz). On those systems
which support read-write access to this object, if there is
an attempt to set this variable to a value that is not
suppo… | scalar | NonNegativeInteger | .0.13891.101.9.2 |
| upsConfigOutputVoltage mandatory The magnitude of the nominal output voltage (RMS Volts).
On those systems which support read-write access to this
object, if there is an attempt to set this variable to
a value … | scalar | NonNegativeInteger | .0.13891.101.9.3 |
| upsConfigOutputFreq mandatory The nominal output frequency (0.1 Hertz). On those systems
which support read-write access to this object, if there is
an attempt to set this variable to a value that is not
sup… | scalar | NonNegativeInteger | .0.13891.101.9.4 |
| upsConfigOutputVA mandatory The magnitude of the nominal Volt-Amp rating (Volt-Amps). | scalar | NonNegativeInteger | .0.13891.101.9.5 |
| upsConfigOutputPower mandatory The magnitude of the nominal true power rating (watts). | scalar | NonNegativeInteger | .0.13891.101.9.6 |
| upsConfigLowBattTime mandatory The value of upsEstimatedMinutesRemaining at which a
lowBattery condition is declared. For agents which
support only discrete (discontinuous) values, then the
agent shall round u… | scalar | NonNegativeInteger | .0.13891.101.9.7 |
| upsConfigLowVoltageTransferPoint mandatory The minimum input line voltage (RMS Volts) allowed before
the UPS system transfers to battery backup. | scalar | NonNegativeInteger | .0.13891.101.9.9 |