lgpEnvRemoteSensorMode

LIEBERT-GP-ENVIRONMENTAL-MIB · .1.3.6.1.4.1.476.1.42.3.4.9.10.1.3

Object

column r/w Enumeration
Function assigned to remote sensor.  When set to control(2) the
sensor will be used in calculation of remote sensor temperature which
may be used for heating and cooling control.  When set to disable(0)
the remote sensor reading is not available.  When set to reference(1)
the remote sensor reading is available but not used for control.

Context

MIB
LIEBERT-GP-ENVIRONMENTAL-MIB
OID
.1.3.6.1.4.1.476.1.42.3.4.9.10.1.3
Type
column
Access
readwrite
Status
current
Parent
lgpEnvRemoteSensorEntry
Table
lgpEnvRemoteSensorTable
Siblings
5

Syntax

Enumeration

Values & Constraints

Enumerated Values
0disable
1reference
2control

Related Objects

Sibling Objects