upsOutputShareCurrentgen

GESINGLEUPS-MIB · .1.3.6.1.4.1.818.1.1.10.4.4.1.8

Object

column Amps SNMPv2-SMIInteger32
In a parallel system ideally all the UPS are requested to 
contribute to the load with the same amount of current, 
i.e. with no current share. The current share occurs when an
UPS exchanges some current with another UPS, so that this 
current component doesn't feed the load. 
The share part of the UPS current represents an undesired UPS
loading, and therefore it should be minimized. If the share 
current is too high, the UPS results overloaded and in some 
conditions (i.e. very high load) the system could turn on 
bypass reducing dramatically the global system reliability.
		PMAD detects the amount of share currents in a parallel system,
		generating an alarm if this value is above a parameter-based threshold.
		Single UPS systems don't have this feature, NA will be provided.(*)