upsStartupAfterDelaysixth
GEPARALLELUPS-MIB ·
.1.3.6.1.4.1.818.1.1.16.8.3
Object
scalar
r/w
sixths Integer32
Setting this object will start the output after the indicated number of sixths, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of sixths until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*)
Context
- MIB
- GEPARALLELUPS-MIB
- OID
.1.3.6.1.4.1.818.1.1.16.8.3- Type
- scalar
- Access
- readwrite
- Status
- current
- Units
- sixths
- Parent
- upsControlsixth
- Siblings
- 12
Syntax
sixths Integer32
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsShutdownTypesixth This object determines the nature of the action to be
taken at the time when the countdown of the
upsShutdownAfterDelay and upsRebootWithDuration
objects reaches zero.
… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.16.8.1 |
| upsBatteryChargeMethodsixth The present state of the charge method. Setting this
object to 'Normal charge' will cause the battery to be
charged using the normal method. Setting this object to
'Boost charg… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.16.8.10 |
| upsInverterOnOffsixth The present state of the inverter. Setting this
object to 'on' will cause the inverter to be turned
on. Setting this object to 'off' will turn the
inverter off. If the inverter i… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.16.8.11 |
| upsBypassOnOffsixth The present state of the bypass. Setting this
object to 'on' will cause the bypass to be activated.
Setting this object to 'off' will deactivate the
bypass. If the UPS is already… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.16.8.12 |
| upsLoadSourcesixth The present source of the load. Setting this
object to 'On bypass' will cause the load to be
supplied by the bypass.
Setting this object to 'On inverter' will cause the
load to… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.16.8.13 |
| upsShutdownAfterDelaysixth Setting this object will shutdown (i.e., turn off)
either the UPS output or the UPS system (as determined
by the value of upsShutdownType at the time of
shutdown) after the indica… | scalar | sixths Integer32 | .1.3.6.1.4.1.818.1.1.16.8.2 |
| upsRebootWithDurationsixth Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of upsShutdownType at the time
of shutdown) for … | scalar | sixths Integer32 | .1.3.6.1.4.1.818.1.1.16.8.4 |
| upsAutoRestartsixth Setting this object to 'on' will cause the UPS system
to restart after a shutdown if the shutdown occurred
during a power loss as a result of either a
upsShutdownAfterDelay or an … | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.16.8.5 |
| upsReceptaclesNumsixth The number of receptacles utilized in this device.
This entry indicates the number of rows in the receptacle
table. | scalar | NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.16.8.6 |
| upsReceptacleSixthTable A list of receptacle table entries. The number of
entries is given by the value of upsReceptacleNum. | table | - | .1.3.6.1.4.1.818.1.1.16.8.7 |
| upsUPSModesixth The operation mode off the UPS. Off-line indicates a
mode in which the input power is transferred to the
output directly or via a step-up or step-down
transformer. On-line mode in… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.16.8.8 |
| upsRectifierOnOffsixth The present state of the rectifier. Setting this
object to 'on' will cause the rectifier to be turned
on. Setting this object to 'off' will turn the