upsShutdownAfterDelayfifth
GEPARALLELUPS-MIB ·
.1.3.6.1.4.1.818.1.1.15.8.2
Object
scalar
r/w
fifths Integer32
Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of fifths, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of fifths remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*)
Context
- MIB
- GEPARALLELUPS-MIB
- OID
.1.3.6.1.4.1.818.1.1.15.8.2- Type
- scalar
- Access
- readwrite
- Status
- current
- Units
- fifths
- Parent
- upsControlfifth
- Siblings
- 12
Syntax
fifths Integer32
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsShutdownTypefifth This object determines the nature of the action to be
taken at the time when the countdown of the
upsShutdownAfterDelay and upsRebootWithDuration
objects reaches zero.
… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.15.8.1 |
| upsBatteryChargeMethodfifth The present state of the charge method. Setting this
object to 'Normal charge' will cause the battery to be
charged using the normal method. Setting this object to
'Boost charg… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.15.8.10 |
| upsInverterOnOfffifth The present state of the inverter. Setting this
object to 'on' will cause the inverter to be turned
on. Setting this object to 'off' will turn the
inverter off. If the inverter i… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.15.8.11 |
| upsBypassOnOfffifth The present state of the bypass. Setting this
object to 'on' will cause the bypass to be activated.
Setting this object to 'off' will deactivate the
bypass. If the UPS is already… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.15.8.12 |
| upsLoadSourcefifth The present source of the load. Setting this
object to 'On bypass' will cause the load to be
supplied by the bypass.
Setting this object to 'On inverter' will cause the
load to… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.15.8.13 |
| upsStartupAfterDelayfifth Setting this object will start the output after the
indicated number of fifths, including starting the
UPS, if necessary. Setting this object to 0 will
cause the startup to occur… | scalar | fifths Integer32 | .1.3.6.1.4.1.818.1.1.15.8.3 |
| upsRebootWithDurationfifth Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of upsShutdownType at the time
of shutdown) for … | scalar | fifths Integer32 | .1.3.6.1.4.1.818.1.1.15.8.4 |
| upsAutoRestartfifth Setting this object to 'on' will cause the UPS system
to restart after a shutdown if the shutdown occurred
during a power loss as a result of either a
upsShutdownAfterDelay or an … | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.15.8.5 |
| upsReceptaclesNumfifth The number of receptacles utilized in this device.
This entry indicates the number of rows in the receptacle
table. | scalar | NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.15.8.6 |
| upsReceptacleFifthTable A list of receptacle table entries. The number of
entries is given by the value of upsReceptacleNum. | table | - | .1.3.6.1.4.1.818.1.1.15.8.7 |
| upsUPSModefifth The operation mode off the UPS. Off-line indicates a
mode in which the input power is transferred to the
output directly or via a step-up or step-down
transformer. On-line mode in… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.15.8.8 |
| upsRectifierOnOfffifth The present state of the rectifier. Setting this
object to 'on' will cause the rectifier to be turned
on. Setting this object to 'off' will turn the
rectifier off. If the rectifi… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.15.8.9 |
Notification Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsBatteryTemperature The ambient temperature at or near the UPS Battery
casing.(*) | scalar | degrees Centigrade SNMPv2-SMIInteger32 | .1.3.6.1.4.1.818.1.1.10.2.7 |