upsRebootWithDurationeighth

GEPARALLELUPS-MIB · .1.3.6.1.4.1.818.1.1.18.8.4

Object

scalar r/w eighths Integer32
Setting this object will immediately shutdown (i.e.,
turn off) either the UPS output or the UPS system (as
determined by the value of upsShutdownType at the time
of shutdown) for a period equal to the indicated
number of eighths, after which time the output will be
started, including starting the UPS, if necessary.  If
the number of eighths required to perform the request
is greater than the requested duration, then the
requested shutdown and startup cycle shall be
performed in the minimum time possible, but in no case
shall this require more than the requested duration
plus 60 eighths.  When read, upsRebootWithDuration
shall return the number of eighths remaining in the
countdown, or -1 if no countdown is in progress.  If
the startup should occur during a utility failure, the
startup shall not occur until the utility power is
restored.(*)

Context

MIB
GEPARALLELUPS-MIB
OID
.1.3.6.1.4.1.818.1.1.18.8.4
Type
scalar
Access
readwrite
Status
current
Units
eighths
Parent
upsControleighth
Siblings
12

Syntax

eighths Integer32

Values & Constraints

No enumerated values or constraints recorded.

Related Objects

Sibling Objects