upsOutputShareCurrentthird
GEPARALLELUPS-MIB ·
.1.3.6.1.4.1.818.1.1.13.4.4.1.8
Object
In a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*)
Context
- MIB
- GEPARALLELUPS-MIB
- OID
.1.3.6.1.4.1.818.1.1.13.4.4.1.8- Type
- column
- Access
- readonly
- Status
- current
- Units
- Amps
- Parent
- upsOutputThirdEntry
- Table
- upsOutputThirdTable
- Siblings
- 7
Syntax
Amps SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsOutputLineIndexthird The output line identifier.(*) | column | PositiveInteger32 | .1.3.6.1.4.1.818.1.1.13.4.4.1.1 |
| upsOutputVoltagethird The present output voltage.(*) | column | RMS Volts NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.13.4.4.1.2 |
| upsOutputCurrentthird The present output current.(*) | column | 0.1 RMS Amp NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.13.4.4.1.3 |
| upsOutputPowerthird The present output true power.(*) | column | Watts NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.13.4.4.1.4 |
| upsOutputPercentLoadthird The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of
the percent load of true power capacity and the
percent load of VA.(*) | column | percent Integer32 | .1.3.6.1.4.1.818.1.1.13.4.4.1.5 |
| upsOutputPowerFactorthird The present output power factor.
The returned value correspond to the cosf of the load.
A positive value indicate an inductive load;
a negative value indicate a capacitive load;… | column | 0.01 cos phi Integer32 | .1.3.6.1.4.1.818.1.1.13.4.4.1.6 |
| upsOutputPeakCurrentthird The present output peak current.(*) | column | Amps SNMPv2-SMIInteger32 | .1.3.6.1.4.1.818.1.1.13.4.4.1.7 |