upsConfigBatteryCapacityseventh
GEPARALLELUPS-MIB ·
.1.3.6.1.4.1.818.1.1.17.9.11
Object
scalar
r/w
Amps Hours NonNegativeInteger32
The installed battery capacity. This value is the 'factory'-value, not the value after calibration.
Context
- MIB
- GEPARALLELUPS-MIB
- OID
.1.3.6.1.4.1.818.1.1.17.9.11- Type
- scalar
- Access
- readwrite
- Status
- current
- Units
- Amps Hours
- Parent
- upsConfigseventh
- Siblings
- 13
Syntax
Amps Hours NonNegativeInteger32
- Source
- NonNegativeInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: 0..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsConfigInputVoltageseventh The magnitude of the nominal input voltage. On those
systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not su… | scalar | RMS Volts NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.17.9.1 |
| upsConfigHighVoltageTransferPointseventh The maximum line voltage allowed before the UPS
system transfers to battery backup.(*) | scalar | RMS Volts NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.17.9.10 |
| upsConfigBatteryChargeCurrentseventh The maximum battery charge current, including external chargers. | scalar | 0.1 Amp DC NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.17.9.12 |
| upsConfigNoLoadShutdownseventh Dis- or enable 'no load' shutdown from the contact interface. | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.17.9.13 |
| upsConfigStartDelayseventh Minimum required autonomy time before the UPS may perform an
autorestart. | scalar | minutes PositiveInteger32 | .1.3.6.1.4.1.818.1.1.17.9.14 |
| upsConfigInputFreqseventh The nominal input frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the re… | scalar | 0.1 Hertz NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.17.9.2 |
| upsConfigOutputVoltageseventh The magnitude of the nominal output voltage. On
those systems which support read-write access to this
object, if there is an attempt to set this variable to
a value that is not s… | scalar | RMS Volts NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.17.9.3 |
| upsConfigOutputFreqseventh The nominal output frequency. On those systems which
support read-write access to this object, if there is
an attempt to set this variable to a value that is not
supported, the r… | scalar | 0.1 Hertz NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.17.9.4 |
| upsConfigOutputVAseventh The magnitude of the nominal Volt-Amp rating.(*) | scalar | Volt-Amps NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.17.9.5 |
| upsConfigOutputPowerseventh The magnitude of the nominal true power rating.(*) | scalar | Watts NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.17.9.6 |
| upsConfigLowBattTimeseventh The value of upsEstimatedMinutesRemaining at which a
lowBattery condition is declared. For agents which
support only discrete (discontinuous) values, then the
agent shall round u… | scalar | minutes NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.17.9.7 |
| upsConfigAudibleStatusseventh The requested state of the audible alarm. When in
the disabled state, the audible alarm should never
sound. The enabled state is self-describing. Setting
this object to muted(3… | scalar | Enumeration | .1.3.6.1.4.1.818.1.1.17.9.8 |
| upsConfigLowVoltageTransferPointseventh The minimum input line voltage allowed before the UPS
system transfers to battery backup.(*) | scalar | RMS Volts NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.17.9.9 |
Notification Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsSecondsOnBatteryseventh If the unit is on battery power, the elapsed time
since the UPS last switched to battery power, or the
time since the network management subsystem was last
restarted, whichever is… | scalar | sevenths NonNegativeInteger32 | .1.3.6.1.4.1.818.1.1.17.2.2 |