pTotalApparentPower
ES-RACKTIVITY-MIB ·
.1.3.6.1.4.1.34097.9.80.1.1.19
Object
Gets the total apparent power of a power module. (unit: VA)
Context
- MIB
- ES-RACKTIVITY-MIB
- OID
.1.3.6.1.4.1.34097.9.80.1.1.19- Type
- column
- Access
- readonly
- Status
- current
- Units
- VA
- Parent
- ePowerEntry
- Table
- ePowerTable
- Siblings
- 87
Syntax
VA SNMPv2-SMIUnsigned32
- Source
- SNMPv2-SMIUnsigned32
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| pGeneralModuleStatus General status of a module. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.1 |
| pApparentEnergy Gets the apparent energy used by an outlet. (unit: 0.001kVAh) | column | kVAh Uthousandth | .1.3.6.1.4.1.34097.9.80.1.1.10 |
| pModuleName Gets, sets or defaults the module name. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.34097.9.80.1.1.10001 |
| pFirmwareVersion Gets the version of the module's firmware. | column | Version | .1.3.6.1.4.1.34097.9.80.1.1.10002 |
| pHardwareVersion Gets the version of a module's hardware. | column | Version | .1.3.6.1.4.1.34097.9.80.1.1.10003 |
| pFirmwareID Gets the ID of the module's firmware. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.34097.9.80.1.1.10004 |
| pHardwareID Gets the ID of a module's hardware. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.34097.9.80.1.1.10005 |
| pPortName Gets, sets or defaults the name of an outlet. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.34097.9.80.1.1.10034 |
| pPortState Sets the state of an outlet: 0=OFF, 1=ON, 2=POWER CYCLE. To get the state of an outlet use CPORTSTAT (CLI) or pStatePortCur (SNMP) (GUID 8) instead. | column | Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10035 |
| pCurrentPriorOff Gets, sets or defaults the priority of an outlet. Priority settings are used when 1 or more outlets must be turned off because the total current of a power module was exceeded. | column | Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10036 |
| pDelayOn Gets, sets or defaults the outlet turn-on delay. Use this to reduce inrush current when the Energy Switch boots. (unit: s) | column | s Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10037 |
| pMaxCurrentOff Gets, sets or defaults the maximum current off level of an outlet. (unit: 0.001A) | column | A Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10038 |
| pMaxCurrentWarning Gets, sets or defaults the maximum current warning level of an outlet. (unit: 0.001A) | column | A Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10039 |
| pMaxPowerOff Gets, sets or defaults the maximum power off level of an outlet. (unit: W) | column | W Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10040 |
| pMaxPowerWarning Gets, sets or defaults the maximum power warning level of an outlet. (unit: W) | column | W Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10041 |
| pMaxTotalCurrentOff Gets, sets or defaults the total maximum current off level of a power module. (unit: 0.001A) | column | A Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10042 |
| pMaxTotalCurrentWarning Gets, sets or defaults the total maximum current warning level of a power module. (unit: 0.001A) | column | A Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10043 |
| pMaxTotalPowerOff Gets, sets or defaults the maximum total power off level. (unit: W) | column | W Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10044 |
| pMaxTotalPowerWarning Gets, sets or defaults the maximum total power warning level. (unit: W) | column | W Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10045 |
| pMaxVoltageWarning Gets, sets or defaults the maximum voltage warning level. (unit: 0.01V) | column | V Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10047 |
| pMinVoltageWarning Gets, sets or defaults the minimum voltage warning level. (unit: 0.01V) | column | V Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10049 |
| pMinTemperatureWarning Gets, sets or defaults the minimum temperature warning level (use DEF accessor to reset). (unit: 0.1K) | column | K Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10052 |
| pMaxTemperatureWarning Gets, sets or defaults the maximum temperature warning level (use DEF accessor to reset). (unit: 0.1K) | column | K Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10053 |
| pPortStateEvent Enables or disables the SNMP trap if the state of an outlet is changed. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10076 |
| pCurrentOffEvent Enables or disables the SNMP trap if the outlet current off level is exceeded. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10077 |
| pCurrentWarningEvent Enables or disables the SNMP trap if the outlet current warning level is exceeded. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10078 |
| pPowerOffEvent Enables or disables the SNMP trap if the power off level is exceeded. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10079 |
| pPowerWarningEvent Enables or disables the SNMP trap if the power warning level is exceeded. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10080 |
| pTotalCurrentOffEvent Enables or disables the SNMP trap if the total outlet current off level is exceeded. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10081 |
| pTotalCurrentWarningEvent Enables or disables the SNMP trap if the total outlet current warning level is exceeded. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10082 |
| pTotalPowerOffEvent Enables or disables the SNMP trap if the total power off level is exceeded. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10083 |
| pTotalPowerWarningEvent Enables or disables the SNMP trap if the total power warning level is exceeded. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10084 |
| pVoltageWarningEvent Enables or disables the SNMP trap if the voltage warning level is exceeded. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10086 |
| pTemperatureWarningEvent Enables or disables the SNMP trap if the temperature warning level is exceeded. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10087 |
| pMaxOverheatingOff Gets, sets or defaults the maximum overheat temperature off level. (unit: 0.1K) | column | K Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10090 |
| pOverheatingOffEvent Enables or disables the SNMP trap if the overtemperature off level is exceeded. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10091 |
| pPowerCycleTime Gets, sets or defaults the time interval that is used to do a power cycle of an outlet. (unit: s) | column | s Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10099 |
| pExternalSensorLabel Gets, sets or defaults the external sensor label. External sensors can be connected to Energy Sensors. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.34097.9.80.1.1.10109 |
| pMaxOverheatingWarning Gets, sets or defaults the overheating temperature warning level. (unit: 0.1K) | column | K Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10121 |
| pOverheatingWarningEvent Enables or disables the SNMP trap if the overheat warning level is exceeded. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10122 |
| pMicroIntTimeThreshold The minimum time the voltage must be interrupted before it is seen as a micro interruption (unit: 0.1ms) | column | ms Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10135 |
| pMicroIntEvent Enables or disables the SNMP trap if a microinterruption on the voltage is detected. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10136 |
| pSoftFuseCurrentThreshold The threshold of the soft fuse is a factor of the maximum nominal current off (unit: A) | column | A Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10137 |
| pSoftFuseDelay The minimum time the current of an outlet must be above the soft fuse current threshold to switch it off. (unit: ms) | column | ms Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10138 |
| pSoftFuseEvent Enables or disables the SNMP trap if a soft fuse is triggered. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10139 |
| pPhaseShiftEvent Enables or disables the SNMP trap if a phase shift on the voltage is detected. | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10140 |
| pSchedulePortOnTime Gets, sets or defaults the time for the scheduler to turn on an outlet. (unit: min) | column | min Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10146 |
| pSchedulePortOffTime Gets, sets or defaults the time for the scheduler to turn off an outlet. (unit: min) | column | min Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10147 |
| pEnableSchedulePort Enables or disables the scheduler on an outlet. When enabled the scheduling is repeated daily. | column | Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10148 |
| pBlockSetPortOff Prevent outlets to be set off (only delay on and powercycle are still possible). | column | Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10161 |
| pSchedulePortChangeEvent event if a port has changed state because of the scheduler | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10166 |
| pAgentIP IP address of the agent associated to this outlet | column | SNMPv2-SMIIpAddress | .1.3.6.1.4.1.34097.9.80.1.1.10172 |
| pAgentPort Network port on which the associated agent will listen | column | Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10173 |
| pAgentCommunicationEventFlags Event flags for events related to agent communication | column | EVENTFLAGS | .1.3.6.1.4.1.34097.9.80.1.1.10174 |
| pAlwaysOn Outlets marked as Always On can only be power cycled by the user | column | Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10175 |
| pGenericTransducerParameters sets the slope of the transducer transfer function when the generic transducer type is selected (unit: mA/V) | column | mA/V Integer32 | .1.3.6.1.4.1.34097.9.80.1.1.10190 |
| pMaxBigCurrentWarning Gets, sets or defaults the maximum current warning level of an outlet. (unit: 0.0001A) | column | A Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10193 |
| pMaxBigPowerWarning Gets, sets or defaults the maximum power warning level of an outlet. (unit: 0.001W) | column | W Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10194 |
| pGroupNumber Group number per port to group ports | column | Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10195 |
| pPhaseLink Link the current port with a voltage phase | column | Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10196 |
| pCurrentSensorSelector Selection of the currentsensor connected to port. To enter your own value you need to use 255 and fill in guid 10190. | column | Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10197 |
| pMinBigCurrentWarning Gets, sets or defaults the minimum current warning level of a port. (unit: 0.0001A) | column | A Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.10209 |
| pTemperature Gets the current temperature of a temperature sensor. (unit: 0.1K) | column | K Utenth | .1.3.6.1.4.1.34097.9.80.1.1.11 |
| pApparentPower Gets the apparent power of an outlet. (unit: VA) | column | VA SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.15 |
| pPowerFactor Gets the power factor of an outlet. (unit: %) | column | % SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.16 |
| pTotalCurrent Gets the total current of a power module. (unit: 0.001A) | column | A Uthousandth | .1.3.6.1.4.1.34097.9.80.1.1.17 |
| pTotalRealPower Gets the total power level of a power module. (unit: W) | column | W SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.18 |
| pSpecificModuleStatus Specific status of a module. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.2 |
| pTotalActiveEnergy Gets the total energy of a power module. (unit: 0.001kWh) | column | kWh Uthousandth | .1.3.6.1.4.1.34097.9.80.1.1.20 |
| pTotalApparentEnergy Gets the total apparent energy of a power module. (unit: 0.001kVAh) | column | kVAh Uthousandth | .1.3.6.1.4.1.34097.9.80.1.1.21 |
| pTotalPowerFactor Gets the total power factor of a power module. (unit: %) | column | % SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.22 |
| pTimeOnline Gets the amount of seconds since the last reset. (unit: s) | column | s SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.24 |
| pCurrentTime Gets or sets the current time (not possible when NTP is enabled). (unit: UNIX) | column | UNIX SNMPv2-SMITimeTicks | .1.3.6.1.4.1.34097.9.80.1.1.3 |
| pVoltage Gets the voltage of a power module. (unit: 0.01V) | column | V Uhundredth | .1.3.6.1.4.1.34097.9.80.1.1.4 |
| pFrequency Gets the frequency of the input voltage of a power module. (unit: 0.001Hz) | column | Hz Uthousandth | .1.3.6.1.4.1.34097.9.80.1.1.5 |
| pTotalHarmonicDistortion total harmonic distortion - outlet (unit: 0.1%) | column | % Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.50 |
| pPhase the phase between 2 waves (unit: degr) | column | degr Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.51 |
| pBigCurrent Gets the current of an outlet. (unit: 0.0001A) | column | A SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.52 |
| pBigPower Gets the power of an outlet. (unit: 0.001W) | column | W Uthousandth | .1.3.6.1.4.1.34097.9.80.1.1.53 |
| pBigApparentPower Gets the apparent power of an outlet. (unit: 0.001VA) | column | VA Uthousandth | .1.3.6.1.4.1.34097.9.80.1.1.54 |
| pDetectedPhase Gives the best matching Phase per currentsensor. Updated every 8s. returnes 255 if no good phaselink is found | column | Unsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.55 |
| pCurrent Gets the current of an outlet. (unit: 0.001A) | column | A Uthousandth | .1.3.6.1.4.1.34097.9.80.1.1.6 |
| powerIndex Index for the selected Power Module | column | Integer32 | .1.3.6.1.4.1.34097.9.80.1.1.65537 |
| powerModuleIndex Selected Power Module | column | Integer32 | .1.3.6.1.4.1.34097.9.80.1.1.65538 |
| pPower Gets the power of an outlet. (unit: W) | column | W SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.34097.9.80.1.1.7 |
| pStatePortCur Gets the current state of an outlet. To toggle an outlet use PORTSTAT (CLI) or pPortstate (SNMP) (GUID 10035) instead. | column | CURPORTSTATE | .1.3.6.1.4.1.34097.9.80.1.1.8 |
| pActiveEnergy Gets the energy used by an outlet. (unit: 0.001kWh) | column | kWh Uthousandth | .1.3.6.1.4.1.34097.9.80.1.1.9 |