pduCircuitBreakerConfigOverloadRestriction

ENLOGIC-PDU-MIB · .1.3.6.1.4.1.38446.1.4.2.1.4

Object

column r/w Enumeration
This OID controls the behavior of a Switched PDU Circuit 
Breaker when an overload condition is possible and additional 
outlets are requested to be turned on. Setting this OID to 
alwaysAllowTurnON (1) will always allow the outlets on the 
corresponding Circuit Breaker to turn on. Setting this OID 
to restrictOnUpperWarning (2) will not allow outlets on the 
corresponding Circuit Breaker to turn on if the 
pduCircuitBreakerConfigUpperWarningThreshold OID is exceeded. 
Setting this OID to restrictOnUpperCritical (3) will not 
allow outlets on the corresponding Circuit Breaker to turn 
on if the pduCircuitBreakerConfigUpperCriticalThreshold OID 
is exceeded. Models that do not support this feature will 
respond to this OID with a value of notSupported (4). 
Attempts to set this OID in these models will fail.