dupsSecondsOnBattery
DeltaUPSv5-MIB ·
.1.3.6.1.4.1.2254.2.5.7.4
Object
scalar
mandatory
1 Second Integer32
If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.
Context
- MIB
- DeltaUPSv5-MIB
- OID
.1.3.6.1.4.1.2254.2.5.7.4- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Units
- 1 Second
- Parent
- dupsBattery
- Siblings
- 18
Syntax
1 Second Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| dupsBatteryCondition mandatory The indication of the capacity remaining in the UPS
system's batteries when AC normal. | scalar | Enumeration | .1.3.6.1.4.1.2254.2.5.7.1 |
| dupsBatteryPosCapacity mandatory An estimate of the positive battery charge remaining
expressed as a percent of full charge. | scalar | 1 Percent Integer32 | .1.3.6.1.4.1.2254.2.5.7.10 |
| dupsBatteryNegCapacity mandatory An estimate of the negative battery charge remaining
expressed as a percent of full charge. | scalar | 1 Percent Integer32 | .1.3.6.1.4.1.2254.2.5.7.11 |
| dupsTemperature mandatory The measurement of internal temperature in the UPS. | scalar | 1 Degrees Centigrade Integer32 | .1.3.6.1.4.1.2254.2.5.7.12 |
| dupsLastReplaceDate mandatory The last battery replacement date. The format is YYYYMMDD. | scalar | OctetString | .1.3.6.1.4.1.2254.2.5.7.13 |
| dupsNextReplaceDate mandatory The next battery replacement date. The format is YYYYMMDD. | scalar | OctetString | .1.3.6.1.4.1.2254.2.5.7.14 |
| dupsBatteryBreaker mandatory Indicate the battery breaker status. | scalar | Enumeration | .1.3.6.1.4.1.2254.2.5.7.15 |
| dupsBatteryCab1Tempurature mandatory Temperature of battery cabnet 1. | scalar | 1 Degrees Centigrade Integer32 | .1.3.6.1.4.1.2254.2.5.7.16 |
| dupsBatteryCab2Tempurature mandatory Temperature of battery cabnet 2. | scalar | 1 Degrees Centigrade Integer32 | .1.3.6.1.4.1.2254.2.5.7.17 |
| dupsBatteryCab3Tempurature mandatory Temperature of battery cabnet 3. | scalar | 1 Degrees Centigrade Integer32 | .1.3.6.1.4.1.2254.2.5.7.18 |
| dupsBatteryCab4Tempurature mandatory Temperature of battery cabnet 4. | scalar | 1 Degrees Centigrade Integer32 | .1.3.6.1.4.1.2254.2.5.7.19 |
| dupsBatteryStatus mandatory The indication of the capacity remaining in the UPS
system's batteries when AC failed. A value of ok
indicates that the remaining run-time is greater than
upsConfigLowBattTime. … | scalar | Enumeration | .1.3.6.1.4.1.2254.2.5.7.2 |
| dupsBatteryCharge mandatory Representing the battery charge status. | scalar | Enumeration | .1.3.6.1.4.1.2254.2.5.7.3 |
| dupsBatteryEstimatedTime mandatory Estimated time from backup to low battery shutdown. | scalar | 1 Minute Integer32 | .1.3.6.1.4.1.2254.2.5.7.5 |
| dupsBatteryPosVoltage mandatory The magnitude of the present positive battery voltage
in 1/10 V. | scalar | 0.1 Volt DC Integer32 | .1.3.6.1.4.1.2254.2.5.7.6 |
| dupsBatteryNegVoltage mandatory The magnitude of the present negative battery voltage
in -1/10 V. | scalar | -0.1 Volt DC Integer32 | .1.3.6.1.4.1.2254.2.5.7.7 |
| dupsBatteryPosCurrent mandatory The present positive battery current in 1/10 A. | scalar | 0.1 Amp DC Integer32 | .1.3.6.1.4.1.2254.2.5.7.8 |
| dupsBatteryNegCurrent mandatory The present negative battery current in 1/10 A. | scalar | 0.1 Amp DC Integer32 | .1.3.6.1.4.1.2254.2.5.7.9 |
Notification Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| IT-WATCHDOGS-V4-MIBccatSensorValue CCAT sensor reading | column | Integer32 | .1.3.6.1.4.1.17373.4.1.7.1.5 |
| IT-WATCHDOGS-V4-MIBccatSensorType CCAT sensor type | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.17373.4.1.7.1.6 |