dupsBypassPower3
DeltaUPSv5-MIB ·
.1.3.6.1.4.1.2254.2.5.6.14
Object
scalar
mandatory
1 Watt Integer32
The bypass line 3 real power of the UPS system in watts. The value -1 indicates this UPS does not support this item.
Context
- MIB
- DeltaUPSv5-MIB
- OID
.1.3.6.1.4.1.2254.2.5.6.14- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Units
- 1 Watt
- Parent
- dupsBypass
- Siblings
- 14
Syntax
1 Watt Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| dupsBypassFrequency mandatory The present bypass frequency in 1/10 Hz.
The value -1 indicates this UPS does not support this item. | scalar | 0.1 Hertz Integer32 | .1.3.6.1.4.1.2254.2.5.6.1 |
| dupsBypassPower2 mandatory The bypass line 2 real power of the UPS system in watts.
The value -1 indicates this UPS does not support this item. | scalar | 1 Watt Integer32 | .1.3.6.1.4.1.2254.2.5.6.10 |
| dupsBypassVoltage3 mandatory The bypass phase 3 voltage of the UPS system in 1/10 V.
The value -1 indicates this UPS does not support this item. | scalar | 0.1 Volt Integer32 | .1.3.6.1.4.1.2254.2.5.6.11 |
| dupsBypassVoltage31 mandatory The bypass line 3-1 voltage of the UPS system in 1/10 V.
The value -1 indicates this UPS does not support this item. | scalar | 0.1 Volt Integer32 | .1.3.6.1.4.1.2254.2.5.6.12 |
| dupsBypassCurrent3 mandatory The bypass line 3 current of the UPS system in 1/10 A.
The value -1 indicates this UPS does not support this item. | scalar | 0.1 Amp Integer32 | .1.3.6.1.4.1.2254.2.5.6.13 |
| dupsBypassSTSTemperature mandatory The measurement of bypass STS temperature.
The value -1 indicates this UPS does not support this item. | scalar | 1 Degree Celsius Integer32 | .1.3.6.1.4.1.2254.2.5.6.15 |
| dupsBypassNumLines mandatory The number of bypass lines utilized in this device. | scalar | Integer32 | .1.3.6.1.4.1.2254.2.5.6.2 |
| dupsBypassVoltage1 mandatory The bypass phase 1 voltage of the UPS system in 1/10 V.
The value -1 indicates this UPS does not support this item. | scalar | 0.1 Volt Integer32 | .1.3.6.1.4.1.2254.2.5.6.3 |
| dupsBypassVoltage12 mandatory The bypass line 1-2 voltage of the UPS system in 1/10 V.
The value -1 indicates this UPS does not support this item. | scalar | 0.1 Volt Integer32 | .1.3.6.1.4.1.2254.2.5.6.4 |
| dupsBypassCurrent1 mandatory The bypass line 1 current of the UPS system in 1/10 A.
The value -1 indicates this UPS does not support this item. | scalar | 0.1 Amp Integer32 | .1.3.6.1.4.1.2254.2.5.6.5 |
| dupsBypassPower1 mandatory The bypass line 1 real power of the UPS system in watts.
The value -1 indicates this UPS does not support this item. | scalar | 1 Watt Integer32 | .1.3.6.1.4.1.2254.2.5.6.6 |
| dupsBypassVoltage2 mandatory The bypass phase 2 voltage of the UPS system in 1/10 V.
The value -1 indicates this UPS does not support this item. | scalar | 0.1 Volt Integer32 | .1.3.6.1.4.1.2254.2.5.6.7 |
| dupsBypassVoltage23 mandatory The bypass line 2-3 voltage of the UPS system in 1/10 V.
The value -1 indicates this UPS does not support this item. | scalar | 0.1 Volt Integer32 | .1.3.6.1.4.1.2254.2.5.6.8 |
| dupsBypassCurrent2 mandatory The bypass line 2 current of the UPS system in 1/10 A.
The value -1 indicates this UPS does not support this item. | scalar | 0.1 Amp Integer32 | .1.3.6.1.4.1.2254.2.5.6.9 |