upsAdvanceSleepAfterDelay

CPS-MIB · .1.3.6.1.4.1.3808.1.1.1.6.2.7

Object

scalar mandatory r/w seconds Integer32
UPS will enter sleep mode after indicated number of seconds,
or less if the UPS batteries become depleted. Setting this
object to 0 will cause the shutdown to occur immediately.  
Setting this object to -1 will abort the countdown.

Context

MIB
CPS-MIB
OID
.1.3.6.1.4.1.3808.1.1.1.6.2.7
Type
scalar
Access
readwrite
Status
mandatory
Units
seconds
Parent
upsAdvanceControl
Siblings
6

Syntax

seconds Integer32

Values & Constraints

Object Constraints
range: -1-600

Related Objects