upsAdvanceSleepAfterDelay
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.1.6.2.7
Object
scalar
mandatory
r/w
seconds Integer32
UPS will enter sleep mode after indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown.
Context
- MIB
- CPS-MIB
- OID
.1.3.6.1.4.1.3808.1.1.1.6.2.7- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Units
- seconds
- Parent
- upsAdvanceControl
Syntax
seconds Integer32
Values & Constraints
Object Constraints
range: -1-600