upsAdvanceInput
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.1.3.2
Object
node
No description available.
Syntax
No syntax metadata recorded.
Values & Constraints
Enumerated Values
1 | other |
2 | unknown |
3 | ok |
4 | nonCritical |
5 | critical |
6 | nonRecoverable |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsBaseInput | node | - | .1.3.6.1.4.1.3808.1.1.1.3.1 |
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAdvanceInputLineVoltage mandatory The input line voltage in 1/10 VAC. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.3808.1.1.1.3.2.1 |
| upsAdvanceInputMaxLineVoltage mandatory The maximum input line voltage in 1/10 VAC over the
previous 1 minute period. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.3808.1.1.1.3.2.2 |
| upsAdvanceInputMinLineVoltage mandatory The minimum input line voltage in 1/10 VAC over the
previous 1 minute period. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.3808.1.1.1.3.2.3 |
| upsAdvanceInputFrequency mandatory The input line frequency in 1/10 Hz. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.3808.1.1.1.3.2.4 |
| upsAdvanceInputLineFailCause mandatory The reason of UPS power failure.
This value is set to:
- noTransfer(1), if UPS is in utility mode.
- highLineVoltage(2), if UPS switch to battery mode by reason of
input voltage… | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.3.2.5 |
| upsAdvanceInputStatus mandatory Display the present status of the utility power supplied to the UPS. | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.3.2.6 |
| upsAdvanceInputWatt mandatory Getting this OID will return the input power that each phase of the UPS can provide. It is represented in Watt. | scalar | RFC1155-SMIGauge | .1.3.6.1.4.1.3808.1.1.1.3.2.7 |