upsAdvanceControlUpsOff
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.1.6.2.1
Object
scalar
mandatory
r/w
Enumeration
UPS will shutdown when the variable is set to turnUpsOff(2). UPS will shutdown after a delay period specified by upsAdvanceConfigShutoffDelay when the variable is Set to turnUpsOffGracefully(3). Without regard to the utility state the UPS will not provide output power in this state. It is no effective to set this value to noTurnUpsOff(1).
Context
- MIB
- CPS-MIB
- OID
.1.3.6.1.4.1.3808.1.1.1.6.2.1- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsAdvanceControl
- Siblings
- 6
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | noTurnUpsOff |
2 | turnUpsOff |
3 | turnUpsOffGracefully |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAdvanceControlRebootUps mandatory UPS will shutdown and turn back on when the variable is
set to rebootUps(2).
It is no effective to set this value to noRebootUps(1). | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.6.2.2 |
| upsAdvanceControlUpsSleep mandatory UPS will enter sleep mode when the variable is set to putUpsToSleep(2).
UPS will enter sleep mode after a delay period specified by
upsAdvanceConfigSleepDelay when the variable … | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.6.2.3 |
| upsAdvanceControlSimulatePowerFail mandatory UPS will transfer to backup mode when the variable is set
to simulatePowerFailure(2).
It is no effective to set this value to noFlashAndBeep(1). | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.6.2.4 |
| upsAdvanceControlFlashAndBeep mandatory UPS will beep and simultaneously turn on the panel lights
when the variable is set to flashAndBeep(2).
It is no effective to set this value to noSimulatePowerFailure(1). | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.6.2.5 |
| upsAdvanceControlTurnOnUPS mandatory UPS will turned on immediately when the variable is set
to turnOnUPS(2).
It is no effective to set this value to noTurnOnUPS(1). | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.6.2.6 |
| upsAdvanceSleepAfterDelay mandatory UPS will enter sleep mode after indicated number of seconds,
or less if the UPS batteries become depleted. Setting this
object to 0 will cause the shutdown to occur immediately. … | scalar | seconds Integer32 | .1.3.6.1.4.1.3808.1.1.1.6.2.7 |