upsAdvanceConfigOutputVoltage
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.1.5.2.1
Object
scalar
mandatory
r/w
Integer32
The standard UPS output voltage in VAC. The possible values are 100, 110, 120, 127, 208, 220, 230, and 240. If a value other than a possible value is set, it will not be accepted.
Context
- MIB
- CPS-MIB
- OID
.1.3.6.1.4.1.3808.1.1.1.5.2.1- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsAdvanceConfig
- Siblings
- 19
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| upsAdvanceConfigShutoffDelay mandatory The delay time the UPS will remain on after receiving a
turn off command. The possible values are between 60 to
5940 seconds.
If a value other than a supported value is set, the… | scalar | RFC1155-SMITimeTicks | .1.3.6.1.4.1.3808.1.1.1.5.2.10 |
| upsAdvanceConfigSleepDelay mandatory The delay time the UPS will enter sleep mode after receiving
a sleep command. WThe possible values are between 60 to
5940 seconds.
If a value other than a supported value is set… | scalar | RFC1155-SMITimeTicks | .1.3.6.1.4.1.3808.1.1.1.5.2.11 |
| upsAdvanceConfigSetEEPROMDefaults mandatory Reset the UPS EEPROM parameters to default values. | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.5.2.12 |
| upsAdvanceConfigAutoRestore mandatory When this option is enabled, the UPS will restore output
immediately when the utility power restores.When this option
is disabled, the UPS will not restore output at that moment… | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.5.2.13 |
| upsAdvanceConfigRechargedCapacity mandatory When the utility power restores, the UPS will start to recharge until
the specified battery capacity in percentage is met before restoring output power.
The possible values are … | scalar | Integer32 | .1.3.6.1.4.1.3808.1.1.1.5.2.14 |
| upsAdvanceConfigColdStart mandatory Set the ability of the UPS can start in the absence of input power.When
this option is enabled the UPS can be turned on without having input power. | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.5.2.15 |
| upsAdvanceConfigDeepDischargeProtection mandatory When the UPS is on Battery Mode with 0% load and the status remains for
the time configured,the RMCARD will enforce the UPS to Sleep Mode and
the output will be turned off. The … | scalar | Integer32 | .1.3.6.1.4.1.3808.1.1.1.5.2.16 |
| upsAdvanceConfigSleepAfterAllClientShut mandatory If this option is enabled, UPS will enter sleep mode after
utility power failed and remaining MSDT+2 minutes.More information
about MSDT please reference to help page of UPS - >… | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.5.2.17 |
| upsAdvanceConfigLowBatteryThreshold mandatory When the UPS supplies battery power and the remaining capacity is lower than this threshold,
the UPS will sound an alarm.
The value expressed in percentage. | scalar | Integer32 | .1.3.6.1.4.1.3808.1.1.1.5.2.18 |
| upsAdvanceConfigEnergyReset mandatory Setting this OID to reset (2) will cause the output energy meter value to be reset to zero.
Getting this OID will do nothing and return the noOperation(1) value. | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.5.2.19 |
| upsAdvanceConfigHighTransferVolt mandatory Adjust the high transfer vloltage in VAC.
The high transfer vloltage will become the UPS default value
subtracts this value. The allowed values depend on the output:
100-127 volt … | scalar | Integer32 | .1.3.6.1.4.1.3808.1.1.1.5.2.2 |
| upsAdvanceConfigBatteryRuntimeThreshold mandatory When the UPS supplies battery power and the remaining runtime is lower than this threshold,
the UPS will sound an alarm.
The value expressed in minutes. | scalar | Integer32 | .1.3.6.1.4.1.3808.1.1.1.5.2.20 |
| upsAdvanceConfigLowTransferVolt mandatory Adjust the low transfer vloltage in VAC.
The low transfer vloltage will become the UPS default value
adds this value. The allowed values depend on the output:
100-127 volt system … | scalar | Integer32 | .1.3.6.1.4.1.3808.1.1.1.5.2.3 |
| upsAdvanceConfigAlarm mandatory This value is set to handle audible alarms when power failure. | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.5.2.4 |
| upsAdvanceConfigAlarmTimer mandatory The time after power failure at which the UPS begins giving
audible alarms. This timer is effective only if the value of
upsAdvanceConfigAlarm is timed(1).
Accepted values are bet… | scalar | RFC1155-SMITimeTicks | .1.3.6.1.4.1.3808.1.1.1.5.2.5 |
| upsAdvanceConfigMinReturnCapacity mandatory The minimum battery capacity that UPS will return from
a low battery shutdown condition. The possible values
are between 0 to 40.
If a value other than a supported value is set, t… | scalar | Integer32 | .1.3.6.1.4.1.3808.1.1.1.5.2.6 |
| upsAdvanceConfigSensitivity mandatory The sensitivity of the UPS to power failure detection. | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.1.5.2.7 |
| upsAdvanceConfigLowBatteryRunTime mandatory The desired run time, in seconds, UPS will enter in a
low battery sequence. The possible values are
120, 300, 420, 600.
If a value other than a supported value is set, the value
w… | scalar | RFC1155-SMITimeTicks | .1.3.6.1.4.1.3808.1.1.1.5.2.8 |
| upsAdvanceConfigReturnDelay mandatory The delay time the UPS will turn on after power recovery.
The value is also used in a 'reboot' or 'wake up' sequence.
The possible values are 0 to 600 seconds.
If a value other th… | scalar | RFC1155-SMITimeTicks | .1.3.6.1.4.1.3808.1.1.1.5.2.9 |