mtrapinfoBmEventId

CPS-MIB · .1.3.6.1.4.1.3808.2.2.6

Object

scalar mandatory Integer32
Allow CPS traps with an integer argument for providing detail
information about Battery Manager specific event identifier. 
Not being defined in the MIB, only reply 0.
          
Known Specific Event ID: Battery Manager
  0 - not used
  1 - Alarm: The battery manager system fault. 
  2 - Info: Device configuration changed. 
  3 - Alarm: Probe configuration mismatched. 
  4 - Info: Probe configuration matched. 
  5 - Alarm: Communication with battery manager has been lost. 
  6 - Info: Communication with battery manager has been restored. 
  7 - Alarm: Communication with LCD has been lost. 
  8 - Info: Communication with LCD has been restored. 
  9 - Warning: Enter battery equalization active mode.
  10- Warning: Leave battery equalization active mode.
  11- Alarm: Battery equalizing has failed. 
  12- Info: Battery equalizing succeeds. 
            
Known Specific Event ID: Battery Probes
  101 - Alarm: Low battery voltage. 
  102 - Alarm: High battery voltage. 
  103 - Info: Battery voltage event has cleared. 
  104 - Alarm: Low battery temperature. 
  105 - Alarm: High battery temperature. 
  106 - Info: Battery temperature event has cleared. 
  107 - Alarm: Critical low battery resistance. 
  108 - Alarm: Critical high battery resistance. 
  109 - Warning: Low battery resistance. 
  110 - Warning: high battery resistance. 
  111 - Info: Battery resistance event has cleared. 
  112 - Alarm: Battery resistance health has crossed alarm threshold. 
  113 - Warning: Battery resistance health has crossed warning threshold. 
  114 - Info: Battery resistance health has returned to Normal.
  115 - Alarm: Battery voltage has under the shutdown threshold for a time. 
  116 - Info: Battery voltage has restored from the shutdown threshold. 
  117 - Alarm: Battery probes has been shut down. 
  118 - Alarm: Low battery soc. 
  119 - Warning: Low battery soc. 
  120 - Info: Battery soc event has cleared. 
          		 
Known Specific Event ID: BM String Voltage 
  201 - Alarm: Low string voltage. 
  202 - Alarm: High string voltage.
  203 - Warning: Low string voltage. 
  204 - Warning: High string voltage.  
  205 - Info: String voltage event has cleared.
  226 - Alarm: Low string soc. 
  207 - Warning: Low string soc. 
  208 - Info: String soc event has cleared.

Context

MIB
CPS-MIB
OID
.1.3.6.1.4.1.3808.2.2.6
Type
scalar
Access
readonly
Status
mandatory
Parent
mtrapinfo
Siblings
6

Syntax

Integer32
Source
COPS-PR-SPPIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647

Related Objects

Sibling Objects