eSwitchOutletState

CPS-MIB · .1.3.6.1.4.1.3808.1.1.2.2.2.1.3

Object

column mandatory RFC1213-MIBDisplayString
Getting this OID will reply the status of all outlets in the switch.
'0' for outlet off, '1' for outlet on.
The index from left to right is outlet#8, #7, #6, #5, #4, #3, #2, #1.
For Example:
If the string is '01011010', it means the outlets status are the following:
outlet #8 is off,
outlet #7 is on,
outlet #6 is off,
outlet #5 is on,
outlet #4 is on,
outlet #3 is off,
outlet #2 is on,
outlet #1 is off.