ePDUOutletStatusActivePower
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.8
Object
Getting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in watts
Context
- MIB
- CPS-MIB
- OID
.1.3.6.1.4.1.3808.1.1.3.3.5.1.1.8- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- ePDUOutletStatusEntry
- Table
- ePDUOutletStatusTable
- Siblings
- 13
Syntax
RFC1155-SMIGauge
- Source
- RFC1155-SMIGauge
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| ePDUOutletStatusIndex mandatory The index to the outlet entry. | column | Integer32 | .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.1 |
| ePDUOutletStatusPeakPower mandatory The peak power consumption of the Rack PDU load in watts.
This value can be reset by setting the oid
ePDUOutletConfigMonitoredPeakLoadReset to reset (2) | column | RFC1155-SMIGauge | .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.10 |
| ePDUOutletStatusPeakPowerTime mandatory Get this oid shows the date and time that peak power consumption occurred | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.11 |
| ePDUOutletStatusPeakPowerStart mandatory Get this oid shows the date and time that peak power consumption started | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.12 |
| ePDUOutletStatusEnergy mandatory Energy meter measuring Rack PDU load energy consumption
in tenths of kilowatt-hours. This value can be reset by setting
the oid ePDUOutletConfigMonitoredEnergyReset to reset (2) | column | RFC1155-SMIGauge | .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.13 |
| ePDUOutletStatusEnergyStartTime mandatory Indicates the date and time of the last device energy
meter reset | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.14 |
| ePDUOutletStatusOutletName mandatory The name of the outlet. The maximum string size is device dependent.
This OID is provided for informational purposes only. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.2 |
| ePDUOutletStatusOutletPhase mandatory The phase/s associated with this outlet.
For single phase devices, this object will always
return phase1(1).
For 3-phase devices, this object will r… | column | Enumeration | .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.3 |
| ePDUOutletStatusOutletState mandatory Getting this variable will return the outlet state. If
the outlet is on, the outletStatusOn (1) value will be returned.
If the outlet is off, the outletStatusOff (2) value will b… | column | Enumeration | .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.4 |
| ePDUOutletStatusCommandPending mandatory Getting this variable will return the command pending
state of the outlet. If a command is pending on the
outlet, the outletStatusCommandPending (1) value
will be returned. If th… | column | Enumeration | .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.5 |
| ePDUOutletStatusOutletBank mandatory The bank associated with this outlet. | column | Integer32 | .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.6 |
| ePDUOutletStatusLoad mandatory Getting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU
in tenths of Amps. | column | RFC1155-SMIGauge | .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.7 |
| ePDUOutletStatusAlarm mandatory Getting this OID will return the current outlet alarm | column | Enumeration | .1.3.6.1.4.1.3808.1.1.3.3.5.1.1.9 |