ePDUOutletPhaseOverloadRestriction

CPS-MIB · .1.3.6.1.4.1.3808.1.1.3.3.2.1.1.2

Object

column mandatory r/w Enumeration
This OID controls the behavior of a Switched Rack PDU
phase when an overload condition is possible and 
additional outlets are requested to be turned on. 
              
Setting this OID to alwaysAllowTurnON (1) will always allow 
the outlets on the corresponding phase to turn on.
              
Setting this OID to restrictOnNearOverload (2) will not allow
outlets on the corresponding phase to turn on if the 
ePDULoadConfigNearOverloadThreshold OID is exceeded.
                     
Setting this OID to restrictOnOverload (3) will not allow
outlets on the corresponding phase to turn on if the 
ePDULoadConfigOverloadThreshold OID is exceeded.

Context

MIB
CPS-MIB
OID
.1.3.6.1.4.1.3808.1.1.3.3.2.1.1.2
Type
column
Access
readwrite
Status
mandatory
Parent
ePDUOutletPhaseEntry
Table
ePDUOutletPhaseTable
Siblings
1

Syntax

Enumeration

Values & Constraints

Enumerated Values
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload

Related Objects

Sibling Objects