ePDUOutletConfigPowerOffTime
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.3.3.4.1.1.5
Object
column
mandatory
r/w
Integer32
The amount of time (in seconds) the outlet will delay
powering off when a command that requires
a turn-off delay is issued.
Allowed values are:
-1 - never power off.
0 - power off immediately.
1 to 7200 - power off up to 7200 seconds after being
commanded.