ePDUOutletConfigMonitoredPeakLoadReset
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.7
Object
column
mandatory
r/w
Enumeration
Setting this OID to reset (2) will cause the existing peak power value
to be replaced by the current load power value.
Getting this oid will do nothing and return noAction (1) if the PDU
support this feature, return notSupport (3) if the PDU do not support
this feature.
Context
- MIB
- CPS-MIB
- OID
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.7- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- ePDUOutletConfigMonitoredEntry
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | noAction |
2 | reset |
3 | notSupport |