ePDUOutletConfigMonitoredOverloadThreshold
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.6
Object
column
mandatory
r/w
Integer32
A threshold that indicates the power consumption of
the load has entered an overload condition. It is
represented in watts. A warning
will be issued when the load is greater than or equal
to the threshold value.
Minimum value must be greater than or equal to the value
returned by the ePDUOutletConfigMonitoredNearOverloadThreshold OID.
Maximum value must be less than or equal to the value
returned by the ePDULoadDevMaxOutletLoad OID.
0 will be returned if the unit is not Outlet Monitored Rack PDU.
Context
- MIB
- CPS-MIB
- OID
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.6- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- ePDUOutletConfigMonitoredEntry
Syntax
Integer32
Values & Constraints
No enumerated values or constraints recorded.