ePDUOutletConfigMonitoredLowLoadThreshold
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.4
Object
column
mandatory
r/w
Integer32
A threshold that indicates the power consumption of
the load is nearing a low consumption condition. It is
represented in watts. A warning will be issued when
the load is less than the threshold value.
A threshold value of 0 effectively disables this
warning.
Maximum value must be less than the value returned
by the ePDUOutletConfigMonitoredNearOverloadThreshold OID.
0 will be returned if the unit is not Outlet Monitored Rack PDU.
Context
- MIB
- CPS-MIB
- OID
.1.3.6.1.4.1.3808.1.1.3.3.4.3.1.4- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- ePDUOutletConfigMonitoredEntry
- Table
- ePDUOutletConfigMonitoredTable
- Siblings
- 7
Syntax
Integer32
- Source
- COPS-PR-SPPIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| ePDUOutletConfigMonitoredIndex mandatory The index to the RACK PDU Phase entry. | column | Integer32 | .1.3.6.1.4.1.3808.1.1.3.3.4.3.1.1 |
| ePDUOutletConfigMonitoredName mandatory The name of the Monitored Outlet. The maximum string size is device dependent.
An error will be returned if the set request exceeds the max size. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.3808.1.1.3.3.4.3.1.2 |
| ePDUOutletConfigMonitoredNumber mandatory The outlet number of an Outlet Monitored RACK PDU. | column | Integer32 | .1.3.6.1.4.1.3808.1.1.3.3.4.3.1.3 |
| ePDUOutletConfigMonitoredNearOverloadThreshold mandatory A threshold that indicates the power consumption of
the load is nearing an overload condition. It is
represented in watts. A warning
will be issued when the load is greater tha… | column | Integer32 | .1.3.6.1.4.1.3808.1.1.3.3.4.3.1.5 |
| ePDUOutletConfigMonitoredOverloadThreshold mandatory A threshold that indicates the power consumption of
the load has entered an overload condition. It is
represented in watts. A warning
will be issued when the load is greater th… | column | Integer32 | .1.3.6.1.4.1.3808.1.1.3.3.4.3.1.6 |
| ePDUOutletConfigMonitoredPeakLoadReset mandatory Setting this OID to reset (2) will cause the existing peak power value
to be replaced by the current load power value.
Getting this oid will do nothing and return … | column | Enumeration | .1.3.6.1.4.1.3808.1.1.3.3.4.3.1.7 |
| ePDUOutletConfigMonitoredEnergyReset mandatory Setting this OID to reset (2) will cause the device energy meter value
to be reset to zero.
Getting this oid will do nothing and return noAction (1) if the PDU
su… | column | Enumeration | .1.3.6.1.4.1.3808.1.1.3.3.4.3.1.8 |