ePDU2PhaseConfigOverloadRestriction

CPS-MIB · .1.3.6.1.4.1.3808.1.1.6.4.2.1.4

Object

column mandatory r/w Enumeration
This OID controls the behavior of a Switched Rack PDU 
phase when an overload condition is possible and 
additional outlets are requested to be turned on. 
              
Setting this OID to alwaysAllowTurnON (1) will always allow 
the outlets on the corresponding phase to turn on.
              
Setting this OID to restrictOnNearOverload (2) will not allow 
outlets on the corresponding phase to turn on if the 
ePDU2PhaseConfigNearOverloadThreshold OID is exceeded.
              
Setting this OID to restrictOnOverload (3) will not allow 
outlets on the corresponding phase to turn on if the 
ePDU2PhaseConfigOverloadThreshold OID is exceeded.
              
Models that do not support this feature will respond to this OID
with a value of notSupported (-1). Attempts to set this OID
in these models will fail.

Context

MIB
CPS-MIB
OID
.1.3.6.1.4.1.3808.1.1.6.4.2.1.4
Type
column
Access
readwrite
Status
mandatory
Parent
ePDU2PhaseConfigEntry
Table
ePDU2PhaseConfigTable
Siblings
7

Syntax

Enumeration

Values & Constraints

Enumerated Values
-1notSupported
1alwaysAllowTurnON
2restrictOnNearOverload
3restrictOnOverload

Related Objects

Sibling Objects