ePDU2BankConfigOverloadRestriction
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.6.5.2.1.4
Object
column
mandatory
r/w
Enumeration
This OID controls the behavior of a Switched Rack PDU
bank when an overload condition is possible and
additional outlets are requested to be turned on.
Setting this OID to alwaysAllowTurnON (1) will always allow
the outlets on the corresponding bank to turn on.
Setting this OID to restrictOnNearOverload (2) will not allow
outlets on the corresponding bank to turn on if the
ePDU2BankConfigNearOverloadThreshold OID is exceeded.
Setting this OID to restrictOnOverload (3) will not allow
outlets on the corresponding bank to turn on if the
ePDU2BankConfigOverloadThreshold OID is exceeded.
Context
- MIB
- CPS-MIB
- OID
.1.3.6.1.4.1.3808.1.1.6.5.2.1.4- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- ePDU2BankConfigEntry
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | alwaysAllowTurnON |
2 | restrictOnNearOverload |
3 | restrictOnOverload |