currMeasureFunction
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.50.3.2.1.7
Object
column
mandatory
r/w
Enumeration
Getting this oid to check the configuration be matched with actual installation. Setting this oid to tell system what the measure target is. For the DC current(prefix as dc), charge/discharge threshold would be considered and used. For the AC current(prefix ad ac), RMS threshold would be considered and used.
Context
- MIB
- CPS-MIB
- OID
.1.3.6.1.4.1.3808.1.1.50.3.2.1.7- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- currMeasureEntry
- Table
- currMeasureTable
- Siblings
- 6
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | dcBatteryStringA |
2 | dcBatteryStringB |
3 | dcBatteryStringC |
4 | dcBatteryStringD |
5 | dcBatteryStringE |
6 | dcBatteryStringF |
7 | dcBatteryStringG |
8 | dcBatteryStringH |
9 | dcReserved |
20 | acInputCurrent |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| currMeasureIndex mandatory The current measurement's index. | column | Integer32 | .1.3.6.1.4.1.3808.1.1.50.3.2.1.1 |
| currMeasureIdentName mandatory The current measurement's current probe name. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.3808.1.1.50.3.2.1.2 |
| currMeasureDescription mandatory Current flow measurement's description. | column | RFC1213-MIBDisplayString | .1.3.6.1.4.1.3808.1.1.50.3.2.1.3 |
| currMeasureAlarmStatus mandatory The current alarm status.
For battery system, abnormal value can be (2) to (9).
For AC measure condition, abnormal value can be (50) to (53). | column | Enumeration | .1.3.6.1.4.1.3808.1.1.50.3.2.1.4 |
| currMeasureChargingState mandatory For battery system to get battery charging state. | column | Enumeration | .1.3.6.1.4.1.3808.1.1.50.3.2.1.5 |
| currMeasureCurrent mandatory Getting this oid to get current measurement, unit in 10mA (0.01 A).
For battery system, negative value indicates the discharge state. | column | Integer32 | .1.3.6.1.4.1.3808.1.1.50.3.2.1.6 |