atsOutletDevCommand
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.5.6.1.6
Object
scalar
mandatory
r/w
Enumeration
Setting this OID to immediateAllOn (2) will turn all outlets
on immediately.
Setting this OID to immediateAllOff (3) will turn all outlets
off immediately.
Setting this OID to immediateAllReboot (4) will reboot all outlets
immediately.
Setting this OID to delayedAllOn (5) will turn all outlets on as
defined by each outlet's atsOutletCfgPowerOnTime OID value.
Setting this OID to delayedAllOff (6) will turn all outlets
off as defined by each outlet's atsOutletCfgPowerOffTime OID value.
Setting this OID to delayedAllReboot (7) will cause a
delayedAllOff command to be performed. Once all outlets are off,
the Switched Rack ATS will then delay the largest
atsOutletCfgRebootDuration OID time, and then perform a
delayedAllOn command.
Setting this OID to cancelAllPendingCommands (8) will cause all pending
commands on the Switched Rack ATS to be canceled.
Getting this OID will return the noCommandAll (1) value.
Context
- MIB
- CPS-MIB
- OID
.1.3.6.1.4.1.3808.1.1.5.6.1.6- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- atsOutletDevice
- Siblings
- 5
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | noCommandAll |
2 | immediateAllOn |
3 | immediateAllOff |
4 | immediateAllReboot |
5 | delayedAllOn |
6 | delayedAllOff |
7 | delayedAllReboot |
8 | cancelAllPendingCommands |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| atsOutletDevTotalOutletNum mandatory The total number of outlets on the ATS. | scalar | Integer32 | .1.3.6.1.4.1.3808.1.1.5.6.1.1 |
| atsOutletDevCtrlOutletNum mandatory The number of controlled outlets on the ATS. | scalar | Integer32 | .1.3.6.1.4.1.3808.1.1.5.6.1.2 |
| atsOutletDevColdStartDelay mandatory The amount of delay, in seconds, between when
power is provided to the ATS and when the ATS
provides basic master power to the outlets.
Allowed values are:
… | scalar | Integer32 | .1.3.6.1.4.1.3808.1.1.5.6.1.3 |
| atsOutletDevColdStartState mandatory The ATS outlet state after coldstart.
Allowed values are:
1 - all outlets on after coldstart.
2 - outlet status same as previous state. | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.5.6.1.4 |
| atsOutletDevLocalCtrl mandatory To configure enable or disable outlet local control function. | scalar | Enumeration | .1.3.6.1.4.1.3808.1.1.5.6.1.5 |