atsOutletCtrlCommand

CPS-MIB · .1.3.6.1.4.1.3808.1.1.5.6.5.1.3

Object

column mandatory r/w Enumeration
Getting this variable will return the outlet state. If 
the outlet is on, the immediateOn (2) value will be returned.
If the outlet is off, the immediateOff (2) value will be
returned. 
              
Setting this variable to immediateOn (2) will immediately turn 
the outlet on.
              
Setting this variable to immediateOff (3) will immediately turn 
the outlet off. 
              
Setting this variable to immediateReboot (4) will immediately 
reboot the outlet.
              
Setting this variable to delayedOn (5) will turn the outlet on
after the ePDUOutletConfigPowerOnTime OID time has elapsed.   
              
Setting this variable to delayedOff (6) will turn the outlet off
after the ePDUOutletConfigPowerOffTime OID time has elapsed.
              
Setting this variable to delayedReboot (7) will cause the 
ATS to perform a delayedOff command, wait the atsOutletCfgRebootDuration 
OID time, and then perform a delayedOn command. 
              
Setting this variable to cancelPendingCommand (8) will cause any
pending command to this outlet to be canceled.

Context

MIB
CPS-MIB
OID
.1.3.6.1.4.1.3808.1.1.5.6.5.1.3
Type
column
Access
readwrite
Status
mandatory
Parent
atsOutletCtrlEntry
Table
atsOutletCtrlTable
Siblings
2

Syntax

Enumeration

Values & Constraints

Enumerated Values
1none
2immediateOn
3immediateOff
4immediateReboot
5delayedOn
6delayedOff
7delayedReboot
8cancelPendingCommand