atsOutletCtrlCommand
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.5.6.5.1.3
Object
column
mandatory
r/w
Enumeration
Getting this variable will return the outlet state. If
the outlet is on, the immediateOn (2) value will be returned.
If the outlet is off, the immediateOff (2) value will be
returned.
Setting this variable to immediateOn (2) will immediately turn
the outlet on.
Setting this variable to immediateOff (3) will immediately turn
the outlet off.
Setting this variable to immediateReboot (4) will immediately
reboot the outlet.
Setting this variable to delayedOn (5) will turn the outlet on
after the ePDUOutletConfigPowerOnTime OID time has elapsed.
Setting this variable to delayedOff (6) will turn the outlet off
after the ePDUOutletConfigPowerOffTime OID time has elapsed.
Setting this variable to delayedReboot (7) will cause the
ATS to perform a delayedOff command, wait the atsOutletCfgRebootDuration
OID time, and then perform a delayedOn command.
Setting this variable to cancelPendingCommand (8) will cause any
pending command to this outlet to be canceled.
Context
- MIB
- CPS-MIB
- OID
.1.3.6.1.4.1.3808.1.1.5.6.5.1.3- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- atsOutletCtrlEntry
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | none |
2 | immediateOn |
3 | immediateOff |
4 | immediateReboot |
5 | delayedOn |
6 | delayedOff |
7 | delayedReboot |
8 | cancelPendingCommand |