atsLoadCfgBankOutletRestriction
CPS-MIB ·
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1.5
Object
column
mandatory
r/w
Enumeration
This OID controls the behavior of a ATS phase when an overload
condition is possible and additional outlets are requested to be
turned on.
Setting this OID to alwaysAllowTurnON (1) will always allow
the outlets on the corresponding phase to turn on.
Setting this OID to restrictOnNearOverload (2) will not allow
outlets on the corresponding phase to turn on if the
ePDULoadConfigNearOverloadThreshold OID is exceeded.
Setting this OID to restrictOnOverload (3) will not allow
outlets on the corresponding phase to turn on if the
ePDULoadConfigOverloadThreshold OID is exceeded.
Context
- MIB
- CPS-MIB
- OID
.1.3.6.1.4.1.3808.1.1.5.5.3.4.1.5- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- atsLoadCfgBankEntry
- Table
- atsLoadCfgBankTable
- Siblings
- 5
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | alwaysAllowTurnON |
2 | restrictOnNearOverload |
3 | restrictOnOverload |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| atsLoadCfgBankTableIndex mandatory The index to the ATS bank entry. | column | Enumeration | .1.3.6.1.4.1.3808.1.1.5.5.3.4.1.1 |
| atsLoadCfgBankLowLoad mandatory A threshold that indicates the power consumption of
the load is nearing a low consumption condition. It is
represented in Amps. A warning will be issued when the
load is less th… | column | Integer32 | .1.3.6.1.4.1.3808.1.1.5.5.3.4.1.2 |
| atsLoadCfgBankNearOverLoad mandatory A threshold that indicates the power consumption of
the load is nearing an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater than… | column | Integer32 | .1.3.6.1.4.1.3808.1.1.5.5.3.4.1.3 |
| atsLoadCfgBankOverLoad mandatory A threshold that indicates the power consumption of
the load has entered an overload condition. It is
represented in Amps. A warning will be issued when the
load is greater tha… | column | Integer32 | .1.3.6.1.4.1.3808.1.1.5.5.3.4.1.4 |
| atsLoadCfgBankEnergyReset mandatory Setting this OID to reset (2) will cause the bank energy meter value to be reset to zero.
Getting this OID will do nothing and return the noOperation(1) value. | column | Enumeration | .1.3.6.1.4.1.3808.1.1.5.5.3.4.1.6 |