upsRecepShedSecsWithRestart

CPQPOWER-MIB · .1.3.6.1.4.1.232.165.3.10.2.1.7

Object

column mandatory r/w Integer32
Setting this value will cause the UPS output to turn off 
after the set number of seconds, then restart (after a UPS-defined
'down time') when the utility is again available.  
Unlike UpsRecepOffDelaySecs, which might or might not,
this object always maps to the XCP 0x8A Load Dump & Restart command,
so the desired shutdown and restart behavior is guaranteed to happen.
Once set, this command cannot be aborted.

Context

MIB
CPQPOWER-MIB
OID
.1.3.6.1.4.1.232.165.3.10.2.1.7
Type
column
Access
readwrite
Status
mandatory
Parent
upsRecepEntry
Table
upsRecepTable
Siblings
6

Syntax

Integer32

Values & Constraints

Object Constraints
range: 0-2147483647

Related Objects

Sibling Objects